Plan Review Notes
Plan Review Notes For Permit 18020359
Permit Number 18020359
Review Stop M
Sequence Number 5
Notes
Date Text
2018-12-11 11:17:564TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18020359
 12/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET MEP-1: THE EXISTING AC #1 SYSTEM CANNOT
 CONDITION THE AIR IN BOTH SUITES 100 AND 110. SUITES
 100 AND 110 ARE SEPARATE TENANT SPACES AND SEPARATE
 ZONES AS DEFINED IN SECTION 202 FBC EC, AND THEREFORE
 REQUIRE INDIVIDUAL AND SEPARATE THERMOSTATIC CONTROLS
 PER SECTION C403.2.4.1 FBC EC. TYPICALY, SEPARATE AC
 SYSTEMS MUST BE PROVIDED FOR EACH ZONE.
  
 2) MEP-1: THE REVISED PLAN INDICATES A MOTORIZED
 "JUMPER" IN THE MAIN SUPPLY DUCT WHICH APPEARS TO BE A
 MISPRINT FOR "MOTORIZED DAMPER". PLEASE NOTE THAT O/A
 BY MANUFACTURER'S SPECIFICATIONS MUST BE INTRODUCED
 INTO THE RETURN AIR SYSTEMS SO THAT IT CAN BECOME
 CONDITIONED AND DEHUMIDIFIED SUPPLY AIR.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  