| 2018-12-11 11:17:56 | 4TH REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18020359 |
| | 12/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) SHEET MEP-1: THE EXISTING AC #1 SYSTEM CANNOT |
| | CONDITION THE AIR IN BOTH SUITES 100 AND 110. SUITES |
| | 100 AND 110 ARE SEPARATE TENANT SPACES AND SEPARATE |
| | ZONES AS DEFINED IN SECTION 202 FBC EC, AND THEREFORE |
| | REQUIRE INDIVIDUAL AND SEPARATE THERMOSTATIC CONTROLS |
| | PER SECTION C403.2.4.1 FBC EC. TYPICALY, SEPARATE AC |
| | SYSTEMS MUST BE PROVIDED FOR EACH ZONE. |
| | |
| | 2) MEP-1: THE REVISED PLAN INDICATES A MOTORIZED |
| | "JUMPER" IN THE MAIN SUPPLY DUCT WHICH APPEARS TO BE A |
| | MISPRINT FOR "MOTORIZED DAMPER". PLEASE NOTE THAT O/A |
| | BY MANUFACTURER'S SPECIFICATIONS MUST BE INTRODUCED |
| | INTO THE RETURN AIR SYSTEMS SO THAT IT CAN BECOME |
| | CONDITIONED AND DEHUMIDIFIED SUPPLY AIR. |
| | |
| | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |