| 2018-11-07 10:03:11 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18020359 |
| | 11/7/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MEP-1: THE UPDATED PLANS SHOW A NEW TENANT |
| | BUILD-OUT. REFER TO SECTION 809.2 FBC-17 EXISTING |
| | BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE |
| | 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | |
| | 2) MEP-1: THE CURRENT PLAN APPEARS TO SHOW THE AIR |
| | DISTRIBUTION SYSTEM FOR THE NEW TENANT SPACE CONNECTED |
| | TO A SYSTEM OUTSIDE OF THE TENANT SPACE. PLEASE CLARIFY |
| | HOW THE SYSTEM IN THE NEW TENANT SPACE WILL BE |
| | CONTROLLED, AND HOW ACCESS FOR SERVICE AND FOR |
| | EMERGENCY SHUTDOWN OF THE SYSTEM WILL BE PROVIDED. |
| | |
| | IN ADDITION TO THE COMMENTS ABOVE, PLEASE ANSWER THESE |
| | QUESTIONS CLEARLY ON THE PLAN AND ALSO IN A RESPONSE |
| | NARRATIVE FROM THE EOR- TWOMEY. |
| | |
| | A) INDICATE HOW O/A IS BEING PROVIDED TO THE SPACE AND |
| | HOW IS IS BEING CONTROLLED- TABLE 403.3.1.1 FBC M, AND |
| | SECTION C403.2.4.2 FBC EC. |
| | |
| | B) SHOW THE LOCATION OF THE THERMOSTAT THAT IS |
| | CONTOLLING THE TEMPERATURE IN THE NEW SPACE- SECTION |
| | C403.2.4.1 FBC EC. |
| | |
| | C) THE PLAN INDICATES RETURN AIR VIA A PLENUM CEILING. |
| | PLEASE PLACE A NOTE PURSUANT TO SECTION 606.2.1 |
| | REGARDING ALLOWABLE MATERIALS IN THE PLENUM SPACE. |
| | |
| | D) SHOW THE RETURN AIR PATH FROM THE NEW TENANT SPACE |
| | BACK TO THE AIR HANDLER- SECTION 601.6 FBC M. |
| | |
| | 3) MEPP-1: PROVIDE AN ENLARGED DETAIL SHOWING THE |
| | TRANSITION DUCT AND THE 16 ROUND DUCT CONNECTIONS TO |
| | THE EXISTING FIRE DAMPER- SECTION 607.5.3 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |