Plan Review Notes
Plan Review Notes For Permit 18020359
Permit Number 18020359
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-06 16:00:34DENIED
 1. AIR ADMITTANCE VALVE MUST BE AN APPROVED DEVICE THAT
 MEETS THE POSITIVE AND NEGATIVE PRESSURE ON A FIVE OR
 MORE MULTI-STORY BUILDING, IF NOT APPROVE IT CANNOT BE
 USED ON THE FIRST FLOOR IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE MANUFACTURES SPECIFICATION UNLESS
 WILLING TO PAY THE COST OF THE DEVICE THAT MEETS THOSE
 REQUIREMENTS. FBC P 918.2 INSTALLATION AND FBC P
 918.3.1 HORIZONTAL BRANCHES.
 2. HOT WATER DEVICE NOT SHOWN, PLEASE PROVIDE DETAIL
 AND SIZING FBC P 607.1 WHERE REQUIRED.
 3. TEMPERED WATER REQUIRED AND DETAILS OF A TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 FBC P
 607.1.2 TEMPERED WATER TEMPERATURE CONTROL.
 4. ADA DETAIL OF HEIGHTS AND DIMENSION NOT SHOWN,
 PLEASE PROVIDE DETAIL DRAWINGS PER 2017 FBC
 ACCESSIBILITY CODE.
 5. THERE IS NO CLEAN OUT AT THE 4? CONNECTION OF THE
 BUILDING 2017 FBC P 708.1.3 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION.
 6. PLEASE DARKEN DIMENSION FOR TOILET ROOM PAGE A-1,
 THEY ARE ILLEGIBLE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 7. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 8. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA
 EXISTING BUILDING CODE 301.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  