| Date |
Text |
| 2018-03-06 16:00:34 | DENIED |
| | 1. AIR ADMITTANCE VALVE MUST BE AN APPROVED DEVICE THAT |
| | MEETS THE POSITIVE AND NEGATIVE PRESSURE ON A FIVE OR |
| | MORE MULTI-STORY BUILDING, IF NOT APPROVE IT CANNOT BE |
| | USED ON THE FIRST FLOOR IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF THE MANUFACTURES SPECIFICATION UNLESS |
| | WILLING TO PAY THE COST OF THE DEVICE THAT MEETS THOSE |
| | REQUIREMENTS. FBC P 918.2 INSTALLATION AND FBC P |
| | 918.3.1 HORIZONTAL BRANCHES. |
| | 2. HOT WATER DEVICE NOT SHOWN, PLEASE PROVIDE DETAIL |
| | AND SIZING FBC P 607.1 WHERE REQUIRED. |
| | 3. TEMPERED WATER REQUIRED AND DETAILS OF A TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 FBC P |
| | 607.1.2 TEMPERED WATER TEMPERATURE CONTROL. |
| | 4. ADA DETAIL OF HEIGHTS AND DIMENSION NOT SHOWN, |
| | PLEASE PROVIDE DETAIL DRAWINGS PER 2017 FBC |
| | ACCESSIBILITY CODE. |
| | 5. THERE IS NO CLEAN OUT AT THE 4? CONNECTION OF THE |
| | BUILDING 2017 FBC P 708.1.3 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. |
| | 6. PLEASE DARKEN DIMENSION FOR TOILET ROOM PAGE A-1, |
| | THEY ARE ILLEGIBLE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 7. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER |
| | FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE. |
| | 8. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA |
| | EXISTING BUILDING CODE 301.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |