| 2018-02-27 11:26:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE 1 AND NOTE 17 SPECIFY THE 2011 NEC. THE NEC |
| | SPECIFIED FOR DESIGN IS NOT THE CURRENT CODE. PROVIDE |
| | CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 2. A CONFLICT EXIST BETWEEN PANEL SCHEDULE AND RISER |
| | DIAGRAM. PANEL SCHEDULE SHOWS # 8 WIRE ON A 60 AMP |
| | BREAKER FEEDING SUB-PANEL IN SUITE 100. RISER SHOWS (3) |
| | 1/0 CONDUCTORS FEEDING THE SAME PANEL. THE # 8 WIRE IS |
| | NOT RATED FOR 60 AMPS, AND THE 1/0 WIRE WOULD NOT FIT |
| | ON A 60 AMP BREAKER. PROVIDE CORRECTION. NEC 110.3, |
| | 215.2, 310.15 |
| | 3. PROVIDE LOAD CALCULATION FOR EXISTING PANEL, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF PANEL IS |
| | ADEQUATE. NEC 215.2, 220, 408.30 |
| | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 5. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |