| Plan Review Notes For Permit 18020355 |
| Permit Number |
18020355 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-22 11:03:46 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- THE DESIGN PRESSURES OF GARAGE DOOR NOA 17-0920.03 | | | SUBMITTED DON'T MEET THE NEGATIVE AND POSITIVE DESIGN | | | PRESSURES REQUIRED FOR A BUILDING LOCATED IN EXPOSURE | | | "D". PROVIDE ANOTHER PRODUCT APPROVAL THAT MEETS THE | | | DESIGN PRESSURES FOR EXPOSURE "D". | | | NOTE: CALCULATIONS SUBMITTED ARE NOT THE RIGHT | | | CALCULATIONS TO BE USED FOR GARAGE DOORS. NEED TO USE | | | TABLE R301.2(4) FBC-RESIDENTIAL, 6TH EDITION (2017) FOR | | | GARAGE DOORS. AND ADJUST THE CALCULATIONS TO THE | | | BUILDING EXPOSURE "D" AND CORRESPONDING MEAN ROOF | | | HEIGHT. OTHERWISE, PROVIDE COMPLETE SIGNED AND SEALED | | | SITE SPECIFIC CALCULATIONS | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|