| 2018-03-14 12:47:57 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SOILS REPORT. |
| | 2. PALM BEACH COUNTY IMPACT FEES REQUIRED. |
| | 3. NOA 14-0414.04 FOR OHD HAS EXPIRED. |
| | 4. NOA 15-0129.04 FOR FIXED WINDOWS HAS EXPIRED. |
| | 5. PROVIDE ICC - ES REPORT FOR ICYNENE INSULATION. |
| | 6. PROVIDE DESIGN WIND LOADS FOR WINOW AND DOOR |
| | OPENINGS, |
| | 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR |
| | GAS BBQ GRILL. |
| | |
| | R401.4 SOIL TESTS. |
| | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL |
| | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, |
| | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE |
| | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL |
| | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE |
| | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. |
| | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN |
| | APPROVED METHOD. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. |
| | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE |
| | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN |
| | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP |
| | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE |
| | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN |
| | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY |
| | IMPACT FEES AT (561) 233-5025. |
| | |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. |
| | |
| | FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF |
| | THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND |
| | DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. |
| | WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL |
| | MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, |
| | THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH |
| | PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE |
| | WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR |
| | HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED |
| | TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR |
| | WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR |
| | WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN |
| | GARAGE DOORS). |
| | |
| | |
| | |
| | |