2018-04-26 11:41:032ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-1 THE NOTE ON THE PLUMBING RISER STATING THE
 PLUMBING LAYOUT WILL BE SUBMITTED AFTER THE
 INSTALLATION WILL NOT COMPLY IN ORDER FOR A PLUMBING
 PERMIT TO BE ISSUED A CODE COMPLIANT SANITARY ISOMETRIC
 SHALL BE SUBMITTED AND APPROVED. 107.3.5.3(12)
  
 2. SHT. A-1 THE SANITARY ISOMETRIC PLEASE CORRECT THE
 FOLLOWING
 A) THE WASTE STACK FOR THE 2ND FLOOR MASTERBATH
 LAVATORY'S, TUB AND WASHING MACHINE SHALL CONNECT TO
 THE BUILDING DRAIN SEPARATELY FROM THE POWDER ROOM BATH
 WET VENT.
 B) THE WASHING MACHINE BRANCH DRAIN SHALL CONNECT TO
 THE WASTE STACK DOWN STREAM OF THE LAVATORY'S AND TUB.
 C) THE POWDER ROOM TOILET SHALL BE VENTED BY THE
 LAVATORY STACK BEFORE CONNECTING TO THE BUILDING DRAIN.
 PER FBC RES P3108.1
  
 3. SHT. A-1 PLACE NOTE ON PLAN SHUT OFF VALVES FOR THE
 STACKABLE WASHING MACHINE SHALL BE ACCESSIBLE. PER FBC
 PL P2903.9.3
  
 4. THE PLUMBING AND GENERAL CONTRACTORS WORKMENS COMP
 INS AND LIBILITY INS NEEDS TO BE UPDATED WITH THE CITY
 OF WPB BEFORE A PERMITS CAN BE ISSUED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  