| Plan Review Notes For Permit 18020313 |
| Permit Number |
18020313 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-26 12:11:40 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 2. THE TANKLESS HEATER SHALL BE MOUNTED A MIN OF 4' | | | FROM ANY OPENING IN BUILDING. PER MANUFACTURE SPEC | | | | | | 3. SHOW ON THE RISER THE LENGTH OF EACH CUT SECTION OF | | | PIPE FROM METER TO MOST REMOTE APPLIANCE. FBC-2017 FUEL | | | GAS, SECS. 402.4.1, 402.4.2. | | | | | | 4. THE TANKLESS WATER HEATER IS NOT SHOWN ON THE GAS | | | RISER IT IS SHOWN ON SHT A-1 NEXT TO THE AC UNITS | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. PLEASE SHOW METER ON THE FLOOR PLAN. PER WPB AMEND | | | TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|