Plan Review Notes
Plan Review Notes For Permit 18020313
Permit Number 18020313
Review Stop G
Sequence Number 2
Notes
Date Text
2018-04-26 12:11:401ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 2. THE TANKLESS HEATER SHALL BE MOUNTED A MIN OF 4'
 FROM ANY OPENING IN BUILDING. PER MANUFACTURE SPEC
  
 3. SHOW ON THE RISER THE LENGTH OF EACH CUT SECTION OF
 PIPE FROM METER TO MOST REMOTE APPLIANCE. FBC-2017 FUEL
 GAS, SECS. 402.4.1, 402.4.2.
  
 4. THE TANKLESS WATER HEATER IS NOT SHOWN ON THE GAS
 RISER IT IS SHOWN ON SHT A-1 NEXT TO THE AC UNITS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE SHOW METER ON THE FLOOR PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  