| Date |
Text |
| 2018-02-09 12:46:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS FOR THIS PERMIT APPEAR TO BE |
| | GENERAL DOCUMENTS OF THE ENTIRE PROJECT. THE |
| | APPLICATION STATES FOR BUILDING # 4, 805 15TH ST; |
| | HOWEVER, IT APPEARS TO BE OF ALL THE BUILDINGS IN THIS |
| | PROJECT. |
| | |
| | |
| | PER NFPA 1 |
| | 1.7.12.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE |
| | SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND |
| | INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF |
| | THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE |
| | CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO |
| | THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT |
| | INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS |
| | NOT INCLUDED. |
| | |
| | PER NFPA 72 |
| | |
| | 7.4.4 SHOP DRAWINGS SHALL INCLUDE THE FOLLOWING |
| | INFORMATION: |
| | (1) NAME OF PROTECTED PREMISES, OWNER, AND OCCUPANT |
| | (WHERE APPLICABLE) |
| | (2) NAME OF INSTALLER OR CONTRACTOR |
| | (3) LOCATION OF PROTECTED PREMISES |
| | |
| | |
| | EACH SUBMITTED PLAN SHALL BE SPECIFIC TO THE BUILDING |
| | THAT IT REPRESENTS. |
| | |
| | |
| | |
| | 2) THE SUBMITTED PLANS DO NOT INCLUDE THE CORRECT |
| | ADDRESS AS REFLECTED ON THE APPLICATION. |
| | |
| | THE ADDRESS ON THE APPLICATION IS 805 15TH ST. THE |
| | ADDRESS ON THE SUBMITTED PLANS IS 808 17TH ST. |
| | |
| | PER NFPA 72 |
| | |
| | 7.4.4 SHOP DRAWINGS SHALL INCLUDE THE FOLLOWING |
| | INFORMATION: |
| | |
| | (3) LOCATION OF PROTECTED PREMISES |
| | |
| | PLEASE PROVIDE THE CORRECT ADDRESS OF THE CORRECT |
| | BUILDING ON THE SUBMITTED SET OF PLANS. |
| | |
| | |
| | |
| | 3) SHEETS FA 2.00A & 2.00 B -THERE IS NO INDICATION OF |
| | THE LOCATION OF THE FAAP IN BUILDING # 1. |
| | |
| | PER NFPA 72 |
| | 7.4.7 CONTROL UNIT DIAGRAMS SHALL BE PROVIDED FOR ALL |
| | CONTROL EQUIPMENT (I.E., EQUIPMENT LISTED AS EITHER A |
| | CONTROL UNIT OR CONTROL UNIT ACCESSORY), POWER |
| | SUPPLIES, BATTERY CHARGERS, AND ANNUNCIATORS AND SHALL |
| | INCLUDE THE FOLLOWING INFORMATION: |
| | (2) LOCATION(S) OF CONTROL EQUIPMENT |
| | |
| | IT IS RECOMMENDED THAT THE FAAP BE LOCATED WITHIN THE |
| | ELECTICAL ROOM ON THE 1ST FLOOR. |
| | |
| | |
| | |
| | |
| | 4) SHEET FA 1.00 - THE IS ONLY ONE FACP AND FAAP FOR |
| | FOUR BUILDINGS. THERE SHOULD BE ONE FACP AND 4 FAAP; |
| | ONE FOR EACH BUILDING. |
| | |
| | PER NFPA 72 |
| | |
| | 10.18.3* ANNUNCIATOR ACCESS AND LOCATION. |
| | 10.18.3.1 ALL REQUIRED ANNUNCIATION MEANS SHALL BE |
| | READILY ACCESSIBLE TO RESPONDING PERSONNEL. |
| | 10.18.3.2 ALL REQUIRED ANNUNCIATION MEANS SHALL BE |
| | LOCATED AS REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION TO FACILITATE AN EFFICIENT RESPONSE TO THE |
| | SITUATION. |
| | |
| | 10.18.5.3 WHERE THE SYSTEM SERVES MORE THAN ONE |
| | BUILDING, EACH BUILDING SHALL BE ANNUNCIATED |
| | SEPARATELY. |
| | |
| | IT IS RECOMMENDED THAT THE FAAP BE LOCATED WITHIN THE |
| | ELECTICAL ROOM ON THE 1ST FLOOR OR AT ANOTHER |
| | ACCEPTABLE AND AGREEABLE LOCATION. |
| | |
| | |
| | |
| | 5) SHEET FA 1.00 - THERE IS AN INDICATION THAT THE |
| | ALARM CAN ONLY BE RESET AT THE FACP |
| | |
| | IT IS RECOMMENDED AND IF POSSIBLE, THAT THE SYSTEM CAN |
| | BE SILENCED AND RESET FROM EACH FAAP. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |