2018-02-28 15:53:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. RISER PROVIDED ONLY SHOWS
 ONE METER CAN, BUT THERE ARE 6 UNITS AND A HOUSE PANEL
 ON THE ORIGINAL PLANS. PROVIDE ACCURATE RISER DIAGRAM.
 NEC 215.5, 230, 250.50, 250.94, 408.30
 2. CURRENT RISER PROVIDED SHOWS THE METER CAN FEEDING
 AN INTERIOR MAIN LUG ONLY PANEL. PROVIDE A MEANS OF
 DISCONNECT PER CODE, WITH A MAXIMUM OF SIX DISCONNECTS
 AT ONE LOCATION. NEC 230.70, 230.71
 3. SHOW LOCATION OF SUB-PANELS IN EACH UNIT. FBC
 107.2.1; NEC 240.24
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 5. PROVIDE ACCURATE LOAD CALCULATION FOR EACH UNIT.
 THIS SHOULD INCLUDE 2 SMALL APPLIANCE CIRCUITS AND THE
 WATER HEATER, WHICH IS NOT SHOWN. THERE IS A DRYER
 LISTED IN THE PANEL SCHEDULE, BUT I DO NOT SEE A DRYER
 ON PLAN. CLARIFY AND/OR CORRECT NEC 220; FBC 107.2.1
 6. SHOW LOCATION OF SERVICE ON FLOOR PLAN. FBC 107.2.1
 7. SHOW LOCATION OF MECHANICAL EQUIPMENT ON PLAN WITH
 REQUIRED GFCI RECEPTACLE FOR SERVICING OF EQUIPMENT.
 NEC 210.63; FBC 107.2.1
 8. RECEPTACLE OUTLETS FOR THE KITCHEN COUNTERTOP ARE
 REQUIRED TO BE ON AT LEAST TWO 20 AMP CIRCUITS AND
 THESE CIRCUITS CANNOT FEED OTHER AREAS. PROVIDE
 CORRECTION. NEC 210.11(C)(1), 210.52(B)
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 13. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 14. PROVIDE PANEL SCHEDULE FOR EACH PANEL INCLUDING THE
 HOUSE PANEL, INDICATING ANY NEW OR ALTERED CIRCUITS,
 THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI
 OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  