| 2018-02-23 07:10:16 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 18020271 |
| | W. P. B. PERMIT: 16060021 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 23/ 2018 |
| | ACTION: DENIED |
| | |
| | HISTORIC 2 STORY R-2 APARTMENT BUILDING |
| | |
| | 1) IT WOULD APPEAR THE PLAN SUBMITTED FOR THIS REVIEW |
| | SHOULD HAVE A LETTER FOR SUCCESSOR ARCHITECT ATTACHED |
| | NOTIFYING THE ORIGINAL ARCHITECT. 61G1-18.002(2) |
| | PROCEDURES FOR A SUCCESSOR ARCHITECT ADOPTING AS HIS |
| | OWN THE WORK OF ANOTHER ARCHITECT. |
| | |
| | 2) SHEET A201 & A202 HAS SEVERAL REFERENCES TO THE |
| | FBC-RESIDENTIAL CODE ALTHOUGH THE TITLE BLOCK INDICATES |
| | THIS PERMIT IS FOR RENOVATIONS TO AN APARTMENT |
| | BUILDING. |
| | 2A) FLOOR PLAN NOTE 8 REFERENCES THE RESIDENTIAL CODE. |
| | 2B) APPLICABLE CODES REFERENCES THE RESIDENTIAL CODE. |
| | 2C) EGRESS NOTES 1 & 2 BOTH REFERENCE THE RESIDENTIAL |
| | CODE. |
| | |
| | 3) WINDOW NOTE # 3 REFERENCES ALL SINGLE HUNG WINDOWS |
| | IN BEDROOMS ARE TO BE CONSIDERED FOR EGRESS WINDOWS. |
| | PLEASE REVIEW UNDER THE 2014 FBC-B SECTION: |
| | 3A) 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 |
| | SQUARE FEET . |
| | EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR |
| | GRADE-FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL |
| | BE 5 SQUARE FEET . |
| | |
| | 3B) 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET CLEAR |
| | OPENING HEIGHT DIMENSION SHALL BE 24 INCHES. THE |
| | MINIMUM NET CLEAR OPENING WIDTH DIMENSION SHALL BE 20 |
| | INCHES. THE NET CLEAR OPENING DIMENSIONS SHALL BE THE |
| | RESULT OF NORMAL OPERATION OF THE OPENING. |
| | |
| | 4) NOTICE ONLY!!!! THE ARCHITECT STATES THE |
| | REQUIREMENTS FOR FLOOR SOUND INSULATION, TO DATE THE |
| | CONTRACTOR HAS NOT SUBMITTED ACTUAL TEST REPORTS FOR |
| | COMPLIANCE WITH: |
| | |
| | 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |