Plan Review Notes
Plan Review Notes For Permit 18020266
Permit Number 18020266
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-09 10:50:38BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 1. CHANGE CODE REFERENCE IN GENERAL COMMENTS TO FBC
 2017 6TH ED.
 2. VERTICAL RE-INFORCEMENT IN CMU WALLS SHALL BE
 CONTINOUS FROM FOUNDATION TO BEAM SUPPORTING ROOF
 FRAMING.
 3. 8 INCH SOLID BLOCK ISOLATES ROOF FROM FOUNDATION
 ELIMINATING UPLIFT REQUIREMENTS.
 4. VERTICAL RE-INFORCING SHALL TERMINATE IN BOND BEAM
 WITH A 90 DEGREE HOOK PER ACI.
 5. PROVIDE VERTICAL DEMENSIONS ON SECTION VIEW.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  