Plan Review Notes
Plan Review Notes For Permit 18020262
Permit Number 18020262
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-02-12 09:00:37PERMIT # 18020262
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET 1.3A: OCCUPANT LOAD AND SEATING DETAILS DO NOT
 MATCH.
 CALCULATIONS LISTED SHOW ALLOWABLE SEATING FOR 75
 PERSONS, BUT THERE ARE 90 SEATS (INCLUDING ACCESSIBLE
 SEATING). AND "TOTAL WITH ACTUAL SEATING" IS LISTED AT
 99. BUT YOUR TOTAL OCCUPANT LOAD IS LISTED AS 86.
 PLEASE MAKE CORRECTIONS. SEATING SHOULD BE FOR 75
 PERSONS. TOTAL OCCUPANT LOAD IS 86.
  
 2) SHEET 1.3A: FIRE ALARM SYSTEM NEEDS TO BE REVIEWED.
 THERE IS A NOTE THAT STATES THAT THERE ARE NO FIRE
 ALARM PULL STATIONS AND ONLY 1 HORN STROBE IS
 INIDICATED. THIS NEEDS TO BE REVIEWED AND VERIFIED THAT
 IT MEETS ALL FIRE CODE AND FIRE ALARM REQUIREMENTS.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  