| Notes |
| Date |
Text |
| 2018-02-12 09:00:37 | PERMIT # 18020262 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | 1) SHEET 1.3A: OCCUPANT LOAD AND SEATING DETAILS DO NOT | | | MATCH. | | | CALCULATIONS LISTED SHOW ALLOWABLE SEATING FOR 75 | | | PERSONS, BUT THERE ARE 90 SEATS (INCLUDING ACCESSIBLE | | | SEATING). AND "TOTAL WITH ACTUAL SEATING" IS LISTED AT | | | 99. BUT YOUR TOTAL OCCUPANT LOAD IS LISTED AS 86. | | | PLEASE MAKE CORRECTIONS. SEATING SHOULD BE FOR 75 | | | PERSONS. TOTAL OCCUPANT LOAD IS 86. | | | | | | 2) SHEET 1.3A: FIRE ALARM SYSTEM NEEDS TO BE REVIEWED. | | | THERE IS A NOTE THAT STATES THAT THERE ARE NO FIRE | | | ALARM PULL STATIONS AND ONLY 1 HORN STROBE IS | | | INIDICATED. THIS NEEDS TO BE REVIEWED AND VERIFIED THAT | | | IT MEETS ALL FIRE CODE AND FIRE ALARM REQUIREMENTS. | | | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|