| 2018-04-16 16:04:15 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED WITH. |
| | |
| | 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | DESIGN MANUAL WAS NOT IN SUBMITTAL PLEASE DOWN LOAD |
| | MANUAL UNDER SUPPORTING DOCUMENTS |
| | |
| | 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE |
| | (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER |
| | FBC PL 316.1.3 AND 919.1 |
| | PLEASE PROVIDE DOCUMENTATION FROM THE MANUFACTURE |
| | STATING THEY REVIEWED AND APPROVED YOUR DESIGN. |
| | |
| | 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE |
| | SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US |
| | FOOD CODE CH 5 AND FBC EX 1010.2 |
| | COULD NOT LOCATE NOTE ON PLAN PLEASE PROVIDE SHEET |
| | NUMBER SHOULD BE LOCATED ON BOTH ISOMETRIC AND FLOOR |
| | PLAN AND AND PROVIDE DETAIL OF WHAT TYPE OF SHIELDING |
| | OR PAN WILL BE USED. |
| | |
| | NEW COMMENT: |
| | 1. SHT. 702 SHOWS THE CONDENSATE RECOVERY PUMP |
| | DISCHARGING INTO THE SANITARY ALL CONDENSATE SHALL |
| | DISCHARGE TO STORM OR TO PERMEABLE GROUND IT IS |
| | PROHIBITED TO DISCHARGE TO THE SANITARY. PER CITY OF |
| | WPB CODE OF ORDINANCE SEC. 90-126. (5) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |