| 2018-04-04 08:22:51 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18020254 |
| | ADD: 1675 PALM BEACH LAKES BLVD. |
| | CONT: STRATICON LLC |
| | TEL: 772-210-0200 STRATICON |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: WED. APRIL 04/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THRESHOLD BUILDING / FL S. S. 553.71(7) |
| | ?THRESHOLD BUILDING". |
| | THE RESPONSE IS THAT THE THRESHOLD DOCUMENTS WERE |
| | SUBMITTED UNDER THE BUCK HOIST PERMIT. PLEASE NOTE THE |
| | SUBMITTED FORMS DATED MARCH 29, 2017 WERE NOT COMPLETE |
| | IN REQUIRED SIGNATURES. |
| | THE CERTIFIED INSPECTION CO. LINE IS LEFT BLANK, NO |
| | NOTARY WORK, CONTRACTOR SIGNATURE WITH NO NOTARY WORK, |
| | MISSING THE ARCHITECT AND ENGINEERS SIGNATURE AND SEAL |
| | AND NOTARY WORK, YOU SHOULD UPDATE YOUR SITE INSPECTOR |
| | INFORMATION WHO IS STILL WITH THE COMPANY, MIKE ADAIR |
| | IS NOW A CITY INSPECTOR. |
| | |
| | |
| | THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE |
| | UPDATE FILES SINCE THEIR MAYBE ADDITIONAL PERSONNEL TO |
| | ACT AS THE JOBSITE INSPECTOR. |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 1A)2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| | THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| | BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| | THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| | ISSUANCE WILL TAKE PLACE. |
| | |
| | 1C)COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | |
| | 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 1F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE |
| | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN |
| | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU |
| | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO |
| | PRINT MAYBE IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 1G) NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND RESHORING |
| | PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| | ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| | RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| | AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 1H)NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM |
| | BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 1I) NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | |
| | |
| | |
| | 2) SHEET 042-LS-111 & 045-A-111: |
| | |
| | 2A-2E) COMPLIED. |
| | |
| | 2F) PROVISO: PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS |
| | 119 & 120 THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH |
| | ALLOWED UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR |
| | THROUGH AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR |
| | EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED |
| | IN ACCORDANCE WITH SECTION 714. THERE SHALL NOT BE |
| | PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS. |
| | |
| | 2G-2K) COMPLIED. |
| | |
| | |
| | 2L) 2ND REQUEST. SEMI-COMPLIED. THE RESPONSE INDICATES |
| | NEW UPDATES FOR WALL TYPE L & L1 ON SHEET A5.02. PLEASE |
| | NOTE THIS SHEET IS NOT IN ORDER, FOUND IT LATER IN THE |
| | REVIEW. |
| | |
| | 2M) COMPLIED. |
| | |
| | 2N) SHEET A-407 NOTICE ONLY!!! SHEET A4.07 MENS STALL |
| | STILL 7 FEET. SHEET A-4.08 WOMENS STALL CORRECTED 7 |
| | FOOT 1 INCH. |
| | 1ST REVIEW COMMENT. THE ENLARGED MENS & WOMENS RESTROOM |
| | ON SHEET A407 & A-408 MEASURE 7-0 OVERALL. THE LAYOUT |
| | JUST BARELY MEETS THE REQUIREMENT FOR THE CLEAR FLOOR |
| | SPACE UNDER THE ACCESSIBILITY CODE SECTION 604.3.1. |
| | DEPENDING ON THE SIZE LAV TO BE INSTALLED THE CLEAR |
| | FLOOR SPACE MAY NOT BE ACHIEVED!!! |
| | |
| | 2O-Q) COMPLIED. |
| | |
| | 2R) 2ND REQUEST. SHEET 042-LS-111 THE FLOOR PLAN SHOWS |
| | A DINING AND BAR AREA, PLEASE PROVIDE COMPLIANCE WITH |
| | THE 2017 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES |
| | ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT |
| | LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING |
| | SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. |
| | |
| | 2S) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND |
| | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES AND WORK SURFACES. |
| | |
| | 2T) 2ND REQUEST. 206.2.5 206.2.5 RESTAURANTS AND |
| | CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN |
| | ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS, |
| | INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR |
| | DINING AREAS. |
| | 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY |
| | WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING |
| | SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, |
| | LUNCH COUNTERS, AND BOOTHS. |
| | 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 2T)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM |
| | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2U) PROVISO, NOTICE ONLY! POOL, GENERATOR, KITCHEN |
| | HOODS, SUPPRESSION, GAS, FENCES, SIGNS, FIRE |
| | SPRINKLERS, FIRE ALARMS, LANDSCAPING, IRRIGATION |
| | PERMITS ARE NOT REVIEWED UNDER THE MAIN BUILDING PERMIT |
| | AND ALL REQUIRE A SEPARATE REVIEW AND FEE. |
| | |
| | 2V)COMPLIED. |
| | |
| | 2W) 2ND REQUEST. SHEET 005-GN-1 BUILDING CODE SUMMARY |
| | INDICATES THE PLANS WERE DEVELOPED A CONSTRUCTION TYPE |
| | II-A, THIS ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A |
| | 4 STORY BUILDING WITH ONE STORY INCREASE, IT WOULD BE |
| | REQUIRED TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017 |
| | FBC-B TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE |
| | REQUIRED TO BE I-B ALLOWABLE 12 STORIES WITH A FULL |
| | NFPA 13 SYSTEM, UNDER THE 2017 WITH FIRE SPRINKLERS A |
| | LL-A BUILDING IS ONLY ALLOWED TO BE 5 STORIES. . |
| | |
| | 2X) COMPLIED. R-1 TRANSIENT A STAY30 DAYS OR LESS, SEE |
| | FBC-B 310.3 & 310.4. |
| | |
| | 2Y)2ND REQUEST. SHEETS 042-ALS-111 NOR SHEET |
| | 045-A-111-A SHOW THE LOCATION OF THE FIRE PUMP |
| | LOCATION. SHEET E-101 SHOWS THE FIRE PUMP IN THE |
| | MECHANICAL/ ELECTRICAL ROOM 127. PLEASE SHOW COMPLIANCE |
| | WITH: |
| | 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL |
| | BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH |
| | SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS. |
| | FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED |
| | FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE |
| | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| | 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 711, OR BOTH. |
| | EXCEPTIONS: |
| | 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY |
| | 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE |
| | PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2. |
| | |
| | 3) SHEET 046-A-111-B: |
| | |
| | 3A) 2ND REQUEST. THE COVERED ENTRY PORT COCHERE SHOWS |
| | THE USE OF A LULA LIFT, PLEASE PROVIDE CONFIRMATION THE |
| | LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION |
| | ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1 |
| | REFERENCED STANDARDS. |
| | |
| | 3B) 2ND REQUEST. SHEET 046-A-111-B SHOWS A NEW FIRE |
| | COMMAND ROOM. |
| | [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND |
| | EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY |
| | WITH SECTIONS 403.4.1 THROUGH 403.4.8. |
| | |
| | 3C)) 2ND REQUEST. [F]403.4.1 SMOKE DETECTION. SMOKE |
| | DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 907.2.13.1. |
| | |
| | 3D) 2ND REQUEST. [F]403.4.2 FIRE ALARM SYSTEM. A FIRE |
| | ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH |
| | SECTION 907.2.13. |
| | |
| | 3E) 2ND REQUEST. [F]403.4.3 STANDPIPE SYSTEM. A |
| | HIGH-RISE BUILDING SHALL BE EQUIPPED WITH A STANDPIPE |
| | SYSTEM AS REQUIRED BY SECTION 905.3. |
| | |
| | 3F)) 2ND REQUEST. [F]403.4.4 EMERGENCY VOICE/ALARM |
| | COMMUNICATION SYSTEM. AN EMERGENCY VOICE/ALARM |
| | COMMUNICATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTION 907.5.2.2. |
| | |
| | 3G) 2ND REQUEST. [F]403.4.5 EMERGENCY RESPONDER RADIO |
| | COVERAGE. EMERGENCY RESPONDER RADIO COVERAGE SHALL BE |
| | PROVIDED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE |
| | COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE |
| | PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | 3I) 2ND REQUEST. 403.4.7 SMOKE REMOVAL. TO FACILITATE |
| | SMOKE REMOVAL IN POST-FIRE SALVAGE AND OVERHAUL |
| | OPERATIONS, BUILDINGS AND STRUCTURES SHALL BE EQUIPPED |
| | WITH NATURAL OR MECHANICAL VENTILATION FOR REMOVAL OF |
| | PRODUCTS OF COMBUSTION IN ACCORDANCE WITH ONE OF THE |
| | FOLLOWING: |
| | 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR |
| | PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF |
| | EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM) |
| | INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL |
| | BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR |
| | FEET (15 240 MM) OF PERIMETER. |
| | |
| | EXCEPTIONS: |
| | 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE |
| | HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE |
| | PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA |
| | IN LIEU OF THE AREA SPECIFIED IN ITEM 1. |
| | 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT |
| | GLAZING CAN BE CLEARED BY FIRE FIGHTERS. |
| | 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE |
| | EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA |
| | INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED |
| | DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER |
| | PORTIONS OF THE BUILDING. |
| | 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE |
| | EQUIVALENT RESULTS. |
| | |
| | 3J) 2ND REQUEST. [F]403.4.8 STANDBY AND EMERGENCY |
| | POWER. A STANDBY POWER SYSTEM COMPLYING WITH SECTION |
| | 2702 AND SECTION 3003 SHALL BE PROVIDED FOR THE STANDBY |
| | POWER LOADS SPECIFIED IN SECTION 403.4.8.3. AN |
| | EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| | SHALL BE PROVIDED FOR THE EMERGENCY POWER LOADS |
| | SPECIFIED IN SECTION 403.4.8.4. |
| | |
| | 3K) 2ND REQUEST. [F]403.4.8.1 EQUIPMENT ROOM. IF THE |
| | STANDBY OR EMERGENCY POWER SYSTEM INCLUDES A GENERATOR |
| | SET INSIDE A BUILDING, THE SYSTEM SHALL BE LOCATED IN A |
| | SEPARATE ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH. SYSTEM SUPERVISION WITH MANUAL |
| | START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE |
| | FIRE COMMAND CENTER. |
| | |
| | 4A-D) COMPLIED. MATRIX PROVIDING THE TOTAL AMOUNT OF |
| | SLEEPING ROOMS ACCESSIBILITY. |
| | |
| | 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 & |
| | 051-A-122: |
| | 5A-F) COMPLIED. |
| | |
| | 6-7) COMPLIED. |
| | |
| | 8) PROVISO/ DEFERRED SUBMITTAL. SHEET A104-A-601 DOOR |
| | STYLE 20 IS A SLIDING BARN DOOR AND TRACK SYSTEM, |
| | HARDWARE GROUP 11 INDICATES ADA COMPLIANT PULLS. THE |
| | DOOR HAS TO MAINTAIN A 32 INCH CLEAR OPENING AS WELL AS |
| | THE HARDWARE MEET COMPLIANCE WITH : |
| | 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE. |
| | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE |
| | PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4. |
| | OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES |
| | MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN |
| | POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND |
| | USABLE FROM BOTH SIDES. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) PROVISO/ DEFERRED SUBMITTAL. WINDOWS ARE UNDER A |
| | SEPARATE PERMITS BUT THERE WILL BE OTHER COMPONENTS AND |
| | CLADDING REQUIREMENTS. 2017 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 11) PROVISO/ DEFERRED SUBMITTAL. W. P. B. 107.3.4.1 |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 12) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS |
| | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |