| 2018-03-12 12:03:06 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN |
| | WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON |
| | THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS |
| | CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED |
| | 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT |
| | SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD |
| | CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT |
| | CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED. |
| | PER FBC PL 1108.1 |
| | |
| | 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB |
| | BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE |
| | GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. |
| | OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE |
| | CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER |
| | FBC ACC 604.5.1 |
| | |
| | 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH |
| | DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL |
| | 405.3.1 |
| | |
| | 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB |
| | BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR |
| | TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN |
| | MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS |
| | WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL |
| | DETAILS. PER FBC ACC 609.4 |
| | |
| | 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM |
| | OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34 |
| | MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3 |
| | |
| | 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR |
| | SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1 |
| | |
| | 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE |
| | WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3 |
| | |
| | 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER |
| | CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1 |
| | |
| | 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR |
| | ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54? |
| | OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL |
| | DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC |
| | 604.5.1 |
| | |
| | 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE |
| | SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF |
| | THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE |
| | CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT |
| | BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC |
| | 609.4 |
| | |
| | 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING |
| | KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3 |
| | |
| | 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON |
| | BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE |
| | ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM |
| | 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1? |
| | WALL THICKNESS. PER FBC ENERGY C404.4 |
| | |
| | 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS |
| | BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE |
| | COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK |
| | IT SHALL CONNECT TO INTAKE OF THE BOILER. PER |
| | MANUFACTURE INSTALL GUIDE |
| | |
| | 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE |
| | (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER |
| | FBC PL 316.1.3 |
| | |
| | 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER |
| | ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON |
| | THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. PER FBC PL 1003.2 |
| | |
| | 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON |
| | BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS |
| | DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM |
| | CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE |
| | ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK. |
| | |
| | 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC |
| | IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE |
| | SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS |
| | TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN |
| | AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY |
| | ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON |
| | THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701, |
| | 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER |
| | DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT |
| | AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC |
| | VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6 |
| | |
| | 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE |
| | SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US |
| | FOOD CODE |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN |
| | WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON |
| | THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS |
| | CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED |
| | 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT |
| | SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD |
| | CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT |
| | CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED. |
| | PER FBC PL 1108.1 |
| | |
| | 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB |
| | BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE |
| | GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. |
| | OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE |
| | CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER |
| | FBC ACC 604.5.1 |
| | |
| | 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH |
| | DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL |
| | 405.3.1 |
| | |
| | 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB |
| | BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR |
| | TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN |
| | MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS |
| | WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL |
| | DETAILS. PER FBC ACC 609.4 |
| | |
| | 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM |
| | OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34 |
| | MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3 |
| | |
| | 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR |
| | SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1 |
| | |
| | 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE |
| | WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3 |
| | |
| | 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER |
| | CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1 |
| | |
| | 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR |
| | ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54? |
| | OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL |
| | DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC |
| | 604.5.1 |
| | |
| | 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE |
| | SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF |
| | THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE |
| | CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT |
| | BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC |
| | 609.4 |
| | |
| | 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING |
| | KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3 |
| | |
| | 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON |
| | BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE |
| | ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM |
| | 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1? |
| | WALL THICKNESS. PER FBC ENERGY C404.4 |
| | |
| | 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS |
| | BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE |
| | COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK |
| | IT SHALL CONNECT TO INTAKE OF THE BOILER. PER |
| | MANUFACTURE INSTALL GUIDE |
| | |
| | 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE |
| | (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER |
| | FBC PL 316.1.3 |
| | |
| | 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER |
| | ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON |
| | THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. PER FBC PL 1003.2 |
| | |
| | 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON |
| | BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS |
| | DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM |
| | CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE |
| | ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK. |
| | |
| | 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC |
| | IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE |
| | SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS |
| | TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN |
| | AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY |
| | ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON |
| | THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701, |
| | 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| | DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| | PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| | MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER |
| | DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT |
| | AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC |
| | VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6 |
| | |
| | 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE |
| | SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US |
| | FOOD CODE |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |