| 2018-03-16 08:56:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. FEED FROM DISCONNECT TO TRANSFORMER T1A IS SHOWN | | | WITH FOUR 3/0 AND ONE #2 WIRE. THIS FEED SHOULD NOT | | | INCLUDE A NEUTRAL CONDUCTOR (GROUNDED CONDUCTOR) AS | | | THIS WOULD CREATE A POSSIBILITY OF OBJECTIONABLE | | | CURRRENT. THIS FEED SHOULD HAVE ONLY THE THREE PHASE | | | CONDUCTORS AND AN EQUIPMENT GROUNDING CONDUCTOR. | | | PROVIDE CORRECTION. NEC 250.6, 250.30 | | | 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE | | | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE | | | CURRENT CODES ABOVE) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|