Plan Review Notes
Plan Review Notes For Permit 18020219
Permit Number 18020219
Review Stop E
Sequence Number 1
Notes
Date Text
2018-03-16 08:56:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEED FROM DISCONNECT TO TRANSFORMER T1A IS SHOWN
 WITH FOUR 3/0 AND ONE #2 WIRE. THIS FEED SHOULD NOT
 INCLUDE A NEUTRAL CONDUCTOR (GROUNDED CONDUCTOR) AS
 THIS WOULD CREATE A POSSIBILITY OF OBJECTIONABLE
 CURRRENT. THIS FEED SHOULD HAVE ONLY THE THREE PHASE
 CONDUCTORS AND AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTION. NEC 250.6, 250.30
 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  