| 2018-03-22 12:55:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. PLAN PROVIDED DOES NOT SHOW ALL WORK DESCRIBED IN |
| | ATTACHED CONTRACT. SHOW ALL ELECTRICAL WORK ON PLAN. |
| | FBC 107.2.1, 107.3.5 (NOT CORRECTED) |
| | 5. PROVIDE PANEL SCHEDULE INDICATING SIZE OF PANEL, ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 215.5, 408.4(NOT ALL CIRCUITS SHOWN) |
| | 6. PROVIDE LOAD CALCULATION FOR SERVICE AND FOR |
| | INDIVIDUAL UNIT, INCLUDE EXISTING AND NEW LOADS TO |
| | CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, |
| | 220, 408.30 (CALCULATION PROVIDED IS NOT PER CODE, |
| | INCLUDE LOAD FOR TANKLESS WATER HEATER. ALSO PROVIDE |
| | LOAD CALC FOR BUILDING SERVICE TO CONFIRM THAT THE |
| | EXISTING SERVICE IS ADEQUATE FOR ADDITION OF TANKLESS |
| | LOAD.) |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |