| 2018-02-26 12:38:00 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. IN NOTE 4 AND THE DESIGN BLOCK THE PLAN SHOWS THE |
| | 2011 NEC FOR DESIGN. THE NEC SPECIFIED FOR DESIGN IS |
| | NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE |
| | (ALSO SEE CURRENT CODES ABOVE) |
| | 2. CARBON MONOXIDE DETECTORS ARE SHOWN IN WRONG |
| | LOCATION. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET |
| | OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| | 3. PER THE 2014 NEC: ?BRANCH CIRCUITS THAT SUPPLY |
| | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| | PROTECTED.? PROVIDE CORRECTION FOR ANY NEW OR ALTERED |
| | CIRCUITS, A NOTE WILL SUFFICE. NEC 210.12 |
| | 4. PLAN PROVIDED DOES NOT SHOW ALL WORK DESCRIBED IN |
| | ATTACHED CONTRACT. SHOW ALL ELECTRICAL WORK ON PLAN. |
| | FBC 107.2.1, 107.3.5 |
| | 5. PROVIDE PANEL SCHEDULE INDICATING SIZE OF PANEL, ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 215.5, 408.4 |
| | 6. PROVIDE LOAD CALCULATION FOR SERVICE AND FOR |
| | INDIVIDUAL UNIT, INCLUDE EXISTING AND NEW LOADS TO |
| | CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, |
| | 220, 408.30 |
| | 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| | 9. BOTH COPIES OF PLAN ARE REQUIRED TO BE SIGNED BY THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. FS 471, 481; FBC |
| | 107.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |