Plan Review Notes
Plan Review Notes For Permit 18020210
Permit Number 18020210
Review Stop E
Sequence Number 1
Notes
Date Text
2018-02-26 12:38:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IN NOTE 4 AND THE DESIGN BLOCK THE PLAN SHOWS THE
 2011 NEC FOR DESIGN. THE NEC SPECIFIED FOR DESIGN IS
 NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 (ALSO SEE CURRENT CODES ABOVE)
 2. CARBON MONOXIDE DETECTORS ARE SHOWN IN WRONG
 LOCATION. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET
 OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 3. PER THE 2014 NEC: ?BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION FOR ANY NEW OR ALTERED
 CIRCUITS, A NOTE WILL SUFFICE. NEC 210.12
 4. PLAN PROVIDED DOES NOT SHOW ALL WORK DESCRIBED IN
 ATTACHED CONTRACT. SHOW ALL ELECTRICAL WORK ON PLAN.
 FBC 107.2.1, 107.3.5
 5. PROVIDE PANEL SCHEDULE INDICATING SIZE OF PANEL, ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4
 6. PROVIDE LOAD CALCULATION FOR SERVICE AND FOR
 INDIVIDUAL UNIT, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30
 7. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 9. BOTH COPIES OF PLAN ARE REQUIRED TO BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. FS 471, 481; FBC
 107.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  