| 2018-02-14 15:03:30 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| | 2017 6TH EDITION |
| | |
| | 1. ONE SET OF PLANS NOT SIGNED AND SEALED BY WILLIAM |
| | TRACY ARCHITECT. |
| | |
| | 61G1-16.001 ARCHITECTS AND INTERIOR DESIGNERS SEAL. |
| | EACH ARCHITECT AND INTERIOR DESIGNER SHALL ACQUIRE A |
| | SEAL WITH WHICH SHE OR HE SHALL IDENTIFY ALL PLANS, |
| | SPECIFICATIONS OR REPORTS PREPARED OR ISSUED BY HER OR |
| | HIM AND FILED FOR PUBLIC RECORD. THE SEAL SHALL BE |
| | CAPABLE OF LEAVING A PERMANENT INK REPRESENTATION OR |
| | OTHER FORM OF EMBOSSING OR OPAQUE AND PERMANENT |
| | IMPRESSION, WHICH ALSO MAY BE COMPUTER GENERATED |
| | IMPRESSIONS, ON THE SURFACE OF PRINTS OR OTHER |
| | DUPLICATIONS OF DRAWINGS, AND, AS APPROPRIATE, UPON |
| | SPECIFICATION PAGES, AND OTHER ARTICLES OF SERVICE. |
| | WHERE REQUIRED, ELECTRONIC FILES MAY BE SEALED IN |
| | ACCORDANCE WITH RULE 61G1-16.005, F.A.C. |
| | |
| | 2. PROVIDE THE FLAME SPREAD INDEX FOR THE US FLOORS |
| | SOUND PROOFING THAT WILL BE USED. |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 |
| | |
| | 3. PROVIDE EXISTING AND NEW STUD SPACING AT SHOWER WALL |
| | LOCATIONS AND INCLUDE TYPE OF BOARD THAT WILL BE USED. |
| | NOTE: MANY CEMENT BOARD MANUFACTURERS REQUIRE A MINIMUM |
| | OF 16 INCHES ON CENTER FOR FRAMING. |
| | FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |