Date Text
2018-03-08 06:08:5803/08/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) LISTED VALUE SEEMS LOW. 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2) ADDRESS REQUIRED TO BE ON PLAN FBC 107.2.1
  
 3) PLAN LIST INCORRECT CODE CYCLE. AS OF DEC,31,2017 WE
 ARE USING THE 2017 FBC 6TH ED.
  
 4) PLUMBING ISOMETRIC IN THE MASTER BATHRROM IS DRY
 VENTED. PER FBC-P 912.2 ALL VENT MUST BE WASHED @ BASE
 OF STACK. FBC-P 912.2
  
 5) SHT M-1 SHOW COPPER RELIEF TO DISCHARGE OUTSIDE. PER
 FBC-R P2804.6.1 THE RELIEF MUST DISCHARGE INTO THE SAME
 ROOM THAT THE HEATER IS IN.
  
 6) PLEASE SHOW THE REQUIRED HEATER PAN AND DISCHARGE
 LINE TO THE OUTSIDE. FBC-R P 2801.6
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  