| 2018-03-01 15:39:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT |
| | CODES ABOVE) |
| | 2. PLAN IS REQUIRED TO SHOW THE ADDRESS OF THE PROJECT. |
| | PROVIDE CORRECTION. FBC 107.2.1 |
| | 3. PANEL SCHEDULE SHOWS AFCI PROTECTION IN SOME AREAS, |
| | BUT DOES NOT SHOW ALL AREAS REQUIRED PER CODE. BRANCH |
| | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC |
| | 210.12; FBC RE E3902.16 |
| | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 5. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH |
| | IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT |
| | 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER. |
| | PROVIDE CORRECTION. NEC 422.13; FBC RE E3702.10 |
| | 6. SMOKE ALARM MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR AND 3 FEET FROM ANY MECHANICAL DUCT OR |
| | CEILING FAN. PROVIDE CORRECTION. FBC RE R314.3(4); NFPA |
| | 72; 29.8.3.4.6,7 |
| | 7. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |