| 2018-02-07 11:36:43 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18020071 |
| | ADD: 7170 OKEECHOBEE BLVD. BLDG. # 1 |
| | CONT: ELEV8 CONSTRUCTION INC. |
| | TEL: 561-430-4870 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2074 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 07/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) SUBMITTED FOR THIS REVIEW IS A FLORIDA APPROVAL FL |
| | 14451-R3 FOR COLONIAL SHUTTERS. ALSO WITHIN THE PRODUCT |
| | APPROVAL PACKAGE IS TECHNICAL SHEETS FOR A BAHAMA |
| | DECORATIVE SHUTTER BUT THERE IS NO FLORIDA APPROVAL |
| | COVERSHEET WITH THIS DOCUMENT. PLEASE PROVIDE THE |
| | FLORIDA PRODUCT APPROVAL COVERSHEET TO IDENTIFY THIS |
| | DOCUMENT. THE SUBMITTED PLAN SHEET L SC-1 SHOW WHERE |
| | THE SHUTTERS WILL BE INSTALLED ON THIS BUILDING. |
| | PLEASE IDENTIFY WHICH TYPE OF SHUTTER STYLE IS BEING |
| | INSTALLED IN WHICH LOCATION. IN MANY LOCATIONS THERE |
| | ARE 3 SHUTTERS BEING INSTALLED IN A ROW, WHICH WOULD |
| | MAKE ME BELIEVE THE BAHAMA SHUTTER, IS BEING INSTALLED |
| | WITH THIS TYPE OF APPLICATION. CENTER OF THE BUILDING |
| | ON THE REAR SIDE THERE IS A DOUBLE SHUTTER; THIS STILL |
| | COULD BE THE BAHAMA STYLE SHUTTER OR THE COLONIAL. |
| | ADDITIONAL INFORMATION IS REQUIRED. IN EITHER CASE |
| | CIRCLE THE APPLICATION TYPE, SIZE, AND PRESSURES |
| | ASSOCIATED WITH THE INSTALLATION AND ANCHOR TYPE. |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) MARK WIENER THE ARCHITECT FOR THIS PROJECT HAS NOT |
| | REVIEWED THIS PRODUCT APPROVAL AND APPLIED THEIR SHOP |
| | DRAWING STAMP OF APPROVAL ON THIS DOCUMENT. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3) SHEET I SC-1 INDICATES APPLYING NEW SCREENS ON THE |
| | EXTERIOR STAIRWELL WINDOWS AS WELL AS EITHER THE BAHAMA |
| | STYLE OR COLONIAL STYLE SHUTTERS. THE PLAN DOES NOT |
| | INDICATE THE SIZE OF THE FLAT STOCK MAKING UP THE |
| | SCREEN ENCLOSURE NOR IS THE AMOUNT OF OPENING THERE IN |
| | EITHER TYPE OF SHUTTER. PLEASE PROVIDE FOR EACH OPENING |
| | THE OPENING SIZE IN SQUARE FEET AT EACH LANDING AND THE |
| | AMOUNT OF REDUCTION THE SCREENING MATERIAL REDUCES THE |
| | OPENING. PLEASE SHOW COMPLIANCE WITH: |
| | 2017 FBC-B SECTION 1027.3 OPEN SIDE. EXTERIOR EXIT |
| | STAIRWAYS AND RAMPS SERVING AS AN ELEMENT OF A REQUIRED |
| | MEANS OF EGRESS SHALL BE OPEN ON NOT LESS THAN ONE |
| | SIDE, EXCEPT FOR REQUIRED STRUCTURAL COLUMNS, BEAMS, |
| | HANDRAILS AND GUARDS. AN OPEN SIDE SHALL HAVE NOT LESS |
| | THAN 35 SQUARE FEET OF AGGREGATE OPEN AREA ADJACENT TO |
| | EACH FLOOR LEVEL AND THE LEVEL OF EACH INTERMEDIATE |
| | LANDING. THE REQUIRED OPEN AREA SHALL BE LOCATED NOT |
| | LESS THAN 42 INCHES ABOVE THE ADJACENT FLOOR OR LANDING |
| | LEVEL. |
| | |
| | 4) THE VALUE OF THIS PERMIT IS $6,000.00 DOLLARS IN |
| | VALUE, THIS SEEMS EXTREMELY LOW. 108.3* BUILDING PERMIT |
| | VALUATION. FOR PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | THE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR FINISHES, |
| | NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |