| 2018-03-06 15:24:18 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #18020063 | | | 3/6/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M204: PROVIDE MINIMUM VENTILATION CALCULATIONS FOR | | | THE NEW AVIS ROOM- TABLE 403.3 | | | | | | 2) SHEET M204: REFER TO SECTION 304.6 AND INDICATE THE | | | HEIGHT OF CU-6-2 ABOVE THE FINISHED FLOOR OF THE GARAGE | | | FLOOR. | | | | | | 3) M218: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION | | | OF CU-24-2 AND THE RACK- SECTION 301.15. | | | | | | 4) SHOW THE LOCATIONS OF FCU- 22-2, 23-2, AND 24-2. | | | | | | 5) REVISE THE AC AND ENERGY CALCULATIONS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|