| 2018-02-22 16:15:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF FIRE SPRINKLER |
| | PROTECTION IN THE THE ELEVATOR CONTROL ROOMS OF THE |
| | AVIS CENTER. |
| | |
| | THIS IS A FULLY SPRINKLERED BUILDING AND SHALL BE |
| | PROVIDED WITH APPLICABLE FIRE SPRINKLER PROTECTION IS |
| | ALL LOCATIONS PER NFPA 101 AND 13. |
| | |
| | PLEASE PROVIDE A REVIEW AND APPLICABLE NOTE. |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION OF FIRE ALARM PROTECTION IN |
| | THE AVIS OFFICE. |
| | |
| | THIS BUILDING IS REQUIRED TO HAVE A COMPLETE FIRE ALARM |
| | AND SHALL BE PROVIDED WITH APPLICABLE PROTECTION IS ALL |
| | LOCATIONS PER NFPA 101 AND 72. |
| | |
| | PLEASE PROVIDE A REVIEW AND APPLICABLE NOTE. |
| | |
| | |
| | 3) DOOR 205, AVIS OFFICE, IS SHOWN WITHIN A RATED CMU |
| | WALL; HOWEVER, THE DOOR SCHEDULE DOES NOT SHOW ANY |
| | RATING. |
| | |
| | THERE HAS BEEN PREVIOUS DISCUSSION REGARDING THIS LOBBY |
| | WALL ABOUT PENETRATIONS BEING RATED AND WHETHER THE |
| | WALL WAS RATED OR NOT. |
| | |
| | PLEASE REVIEW THIS LOBBY WALL AND ENSURE THE DOOR IS |
| | APPLICABLY RATED. |
| | |
| | |
| | |
| | 4) ANY FIRE SPRINKLER AND/OR FIRE ALARM WORK SHALL BE |
| | DONE UNDER SEPARATE SHOP DRAWING REVISIONS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |