| Plan Review Notes For Permit 18020063 |
| Permit Number |
18020063 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-17 15:25:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. A215, THE OTHER LIFE SAFETY SHEETS INCLUDE FIRE | | | RATINGS REQUIRED FOR WALLS; PLEASE ADD. THE ELEVATOR | | | CONTROL ROOM REQUIRES A FIRE BARRIER, FBC B 3006.4. | | | | | | 2. REVISE THE BUILDING SUMMARY CODE INFORMATION TO | | | REFLECT THE CHANGE IN SQUARE FOOT AREA - AVIS OFFICE IS | | | BUSINESS OCCUPANCY, THIS AREA WAS PREVIOUSLY S2 PARKING | | | GARAGE, FBC 107. THE SQUARE FOOT AREA TOTALS FOR THE | | | BUILDING SHOULD BE CHANGED AS WELL AS ANY OTHER | | | AFFECTED PAGES. | | | | | | 3. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS | | | REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT, | | | IF FEES ARE DUE, TO BE PROVIDED. 561-233-5025 FOR MORE | | | INFORMATION. | | | | | | | | | | | | | | | |
|