Plan Review Notes For Permit 18020061
Permit Number 18020061
Review Stop P
Sequence Number 1
Notes
Date Text
2018-02-16 13:38:2902/16/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) YOUR ISOMETRIC DRAWING SHOWS THE VENT FOR THE MASTER
 BATHROOM SHOWER AS BEING DRY VENTED. THE BASED OF THE
 VENT MUST BE WASHED AND COMPLY WITH 912.2.1. YOU CAN
 SIMPLE REMOVE THE VENT ALTOGETHER AND THE SHOWER WOULD
 BE ON THE HORIZONTAL WET VENT OF THE BATHRROM GROUP.
  
 2) PROVIDE BOTH MANUFACTURE SPECS AND INSTALLATION
 MANUAL FOR THE TANKLESS WATER HEATER. IT MUST BE
 CAPABLE OF PRODUCING HOT WATER (110 MIN) AS DEFINED AND
 REQUIRED FBC-P 607.1 WITH THE SYSTEM AT FULL DEMAND AS
 REQUIRED FBC-P 604.3
  
  