| Plan Review Notes For Permit 18020061 |
| Permit Number |
18020061 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-16 13:38:29 | 02/16/2018 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) YOUR ISOMETRIC DRAWING SHOWS THE VENT FOR THE MASTER | | | BATHROOM SHOWER AS BEING DRY VENTED. THE BASED OF THE | | | VENT MUST BE WASHED AND COMPLY WITH 912.2.1. YOU CAN | | | SIMPLE REMOVE THE VENT ALTOGETHER AND THE SHOWER WOULD | | | BE ON THE HORIZONTAL WET VENT OF THE BATHRROM GROUP. | | | | | | 2) PROVIDE BOTH MANUFACTURE SPECS AND INSTALLATION | | | MANUAL FOR THE TANKLESS WATER HEATER. IT MUST BE | | | CAPABLE OF PRODUCING HOT WATER (110 MIN) AS DEFINED AND | | | REQUIRED FBC-P 607.1 WITH THE SYSTEM AT FULL DEMAND AS | | | REQUIRED FBC-P 604.3 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|