| 2018-02-15 15:27:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC |
| | 210.12; FBC RE E3902.16 |
| | 2. RECEPTACLES IN GARAGE, INCLUDING THE GARAGE DOOR |
| | OPENER, REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. |
| | NEC 210.8; FBC RE E3902.2 |
| | 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 4. LIGHTING OVER MASTER TUB IS SHOWN AS A RECESS LIGHT. |
| | LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| | FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D); |
| | FBC RE E4003.11 |
| | 5. SMOKE ALARM MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR. PROVIDE CORRECTION. FBC RE R314.3(4) |
| | 6. PANEL SCHEDULE STATES THAT THERE ARE 4 SMALL |
| | APPLIANCE CIRCUITS. EACH OF THESE CIRCUITS IS REQUIRED |
| | TO BE INCLUDED IN THE LOAD CALCULATION. PROVIDE |
| | CORRECTION. NEC 220, FBC RE E3602.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |