Plan Review Notes
Plan Review Notes For Permit 18020061
Permit Number 18020061
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-27 10:30:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC-R401.3 DRAINAGE. SURFACE
 DRAINAGE SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE
 OR OTHER APPROVED POINT OF COLLECTION THAT DOES NOT
 CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE
 WATER AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL
 A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET
 (3048 MM). EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR
 OTHER PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF
 FALL WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL
 BE CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE
 STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM)
 OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
 FBC 107.2.5 THE CONSTRUCTION DOCUMENTS SUBMITTED WITH
 THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A
 SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY.
  
 2) SHOW THAT THE DOOR FROM THE GARAGE TO THE DWELLING
 COMPLIES WITH FBC-R302.5.
  
 3) THE ROOF SLOPE IS SPECIFIED AS 5/12 ON SHEET 2-4 AND
 THE TYPICAL WALL SECTION ON SHEET 3-4 HAS 6/12. IN
 ORDER TO AVOID CONFUSION, PLEASE COORDINATE THE ROOF
 SLOPE. FBC 107.2.1
  
 4) ON SHEET 3-4, THE L-12 LINTEL FOR THE 12 FT. WIDE
 SECTIONAL GARAGE DOOR OPENING IS NOT LISTED IN THE
 LINTEL SCHEDULE. FBC-R606.10
  
 5) THE ROOF FRAMING PLAN ON SHEET 4-4, SHOWS TWO HETAL
 20 ANCHORS FOR AN UPLIFT OF 3600 LBS. THE 2017 SIMPSON
 CATELOG LISTS THE UPLIFT CAPACITY FOR TWO HETAL 20
 ANCHORS IN GFMU (GROUT FILLED MASONRY UNITS) AS 2500
 LBS. PLEASE CORRECT. FBC-R802.11.1.1
  
 6) ENERGY FORM R405-2017 LISTS THE A/C DUCT INSULATION
 AS R-8 AND THE MECHANICAL NOTES ON SHEET M-1 SPECIFIES
 R-6. PLEASE CLARIFY. FBC 107.2.1
  
 7) THE PRODUCT APPROVAL FOR THE SLIDING GLASS DOOR
 (FL15332-R4), HAS A DESIGN PRESSURE OF + AND - 35 PSF
 AND THE PLANS REQUIRE +37.8 AND -41.0 PSF. THIS SLIDING
 GLASS DOOR IS NOT LARGE MISSILE IMPACT RATED. IT WILL
 REQUIRE IMPACT PROTECTION. FBC-R301.2.1 AND R301.2.1.2
  
 8) THE PRODUCT APPROVAL FOR THE CLOPAY SECTIONAL GARAGE
 DOOR (FL5678-R3) IS FOR THE 2014 FBC AND (FL5678-R4)
 THE ONE FOR THE 2017 FBC IS REQUIRED. THE PLANS REQUIRE
 DESIGN PRESSURES OF +37.8 AND - 50.61 PSF AND THE
 PRODUCT APPROVAL IS FOR +37 AND -42 PSF, WHICH ARE NOT
 ADEQUATE. FBC-R301.2.1
  
 9) THE PRODUCT APPROVAL FOR THE JELD-WEN EXTERIOR DOOR
 (FL 11136-R5) IS FOR THE 2014 FBC AND (FL11136-R7) THE
 ONE FOR THE 2017 FBC IS REQUIRED. FS CHAPTER 553
  
  
  