| 2018-08-03 12:08:52 | 2ND REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: 3RD REQUEST PREVIOUS COMMENTS NOT |
| | COMPLIED WITH. RESPONSE LETTER STATED THAT COMMENTS HAD |
| | BEEN CORRECTED, THE PLANS DID NOT REFLECT THE |
| | RESPONSES. |
| | |
| | 1. THE GAS RISER SHALL HAVE THE FOLLOWING INFORMATION |
| | ON IT TO SHOW CODE COMPLIANCE. |
| | A) SHOW THE LENGTH OF CUT SECTION OF PIPE. |
| | B) SHOW TYPE OF PIPE. |
| | C) SHOW SYSTEM PRESSURE. |
| | D) SHOW SHUT OF VALVES, DRIP LEGS AND REGULATORS. |
| | PER FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. AND WPB |
| | AND TO FBC 107.2.1 |
| | |
| | 2. PROVIDE SIZING TABLES USED IN SIZING NEW PIPING. PER |
| | FBC-2017 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES |
| | 402.4(1) THRU 402.4(37). |
| | |
| | 3. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RELOCATED WATER HEATER. PER FBC-2017 FUEL GAS CODE SEC. |
| | 304. |
| | |
| | NEW COMMENT: |
| | |
| | 1. SHT. P 4.1 DETAIL #3 SHOWS GAS PIPING RUNNING ON TOP |
| | OF THE ROOF BUT THE RISER AND FLOOR PLAN SHOWS THE |
| | PIPING RUNNING UNDER THE ROOF. PLEASE CLARIFY PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. P 4.1 DETAIL #4 THE GAS SCHEDULE SHOWS TOTAL OF |
| | 1245 UNDER REMARKS IT SHOWS 1230 PLEASE CLARIFY PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |