Plan Review Notes
Plan Review Notes For Permit 18020060
Permit Number 18020060
Review Stop P
Sequence Number 2
Notes
Date Text
2018-05-23 15:29:522ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
 1. PROVIDE MANUFACTURE SPECIFICATIONS FOR PREFABRICATED
 BACKFLOW PANEL SHALL MEET NSF 372/61 LEAD FREE
 REQUIREMENTS. THEY SHALL BE ON JOBSITE PRIOR TO 1ST
 ROUGH INSPECTION.
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE ECO-POWER
 SENSOR LAVATORY FAUCETS SHALL MEET NSF 372 AND ASSE
 1070.
 3. THE MOP SINK SHALL COMPLY WITH FBC PL 405.9.
 4. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMER VALVE PER
 FBC PL 1002.4.1.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  