| Plan Review Notes For Permit 18020060 |
| Permit Number |
18020060 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-24 17:31:05 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: 2ND REQUEST PREVIOUS COMMENTS NOT | | | COMPLIED WITH. | | | | | | 1. THE GAS RISER SHALL HAVE THE FOLLOWING INFORMATION | | | ON IT TO SHOW CODE COMPLIANCE. | | | A) SHOW THE LENGTH OF CUT SECTION OF PIPE. | | | B) SHOW TYPE OF PIPE. | | | C) SHOW SYSTEM PRESSURE. | | | D) SHOW SHUT OF VALVES, DRIP LEGS AND REGULATORS. | | | PER FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. AND WPB | | | AEND TO FBC 107.2.1 | | | | | | 2. PROVIDE SIZING TABLES USED IN SIZING NEW PIPING. PER | | | FBC-2017 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES | | | 402.4(1) THRU 402.4(37). | | | | | | 3. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | RELOCATED WATER HEATER. PER FBC-2017 FUEL GAS CODE SEC. | | | 304. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|