Plan Review Notes
Plan Review Notes For Permit 18020060
Permit Number 18020060
Review Stop G
Sequence Number 2
Notes
Date Text
2018-05-24 17:31:051ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: 2ND REQUEST PREVIOUS COMMENTS NOT
 COMPLIED WITH.
  
 1. THE GAS RISER SHALL HAVE THE FOLLOWING INFORMATION
 ON IT TO SHOW CODE COMPLIANCE.
 A) SHOW THE LENGTH OF CUT SECTION OF PIPE.
 B) SHOW TYPE OF PIPE.
 C) SHOW SYSTEM PRESSURE.
 D) SHOW SHUT OF VALVES, DRIP LEGS AND REGULATORS.
 PER FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. AND WPB
 AEND TO FBC 107.2.1
  
 2. PROVIDE SIZING TABLES USED IN SIZING NEW PIPING. PER
 FBC-2017 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(37).
  
 3. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RELOCATED WATER HEATER. PER FBC-2017 FUEL GAS CODE SEC.
 304.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  