Plan Review Notes
Plan Review Notes For Permit 18020060
Permit Number 18020060
Review Stop E
Sequence Number 2
Notes
Date Text
2018-05-18 10:55:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SEVERAL LOCATIONS ON PLAN SHOW THE NEC USED FOR
 DESIGN AS OLDER CODES. THE CURRENT NEC IN EFFECT IS THE
 2014 NEC. REMOVE ALL REFERENCES TO OLDER VERSIONS OF
 THE CODE. FBC PREFACE, 107.2.1 (SHEET T-1.1 STILL SHOWS
 THE 2011 NEC AS BASIS FOR DESIGN. PROVIDE CORRECTION.)
 2. CORRECTED.
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE,
 AND FOR PROPER MARKING OF EQUIPMENT PER CODE. NEC
 110.9, 110.10, 110.16, 110.24 (THIS WILL BE A DEFERRED
 SUBMITTAL AS DISCUSSED AND WILL SHOW AS A PROVISO ON
 PLAN. NO FURTHER ACTION NECESSARY AT THIS TIME.)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED, NOT APPLICABLE.
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94 (NOTE ADDED TO PLAN
 STATES: "INTERLOCK COMMUNICATION SYSTEM GROUND WITH
 MAIN GROUND SYSTEM." THIS DOES NOT FULFILL THE
 REQUIREMENT PER CODE. AN INTERSYSTEM BONDING
 TERMINATION POINT MUST BE LOCATED AT THE SERVICE. SEE
 250.94)
 8. IT APPEARS THE 1200 AMP SERVICE IS LOCATED OUTSIDE.
 PROVIDE DETAILS OF ENCLOSURE RATING FOR THIS
 ENVIRONMENT. NEC 110.3, 110.28 (NOTE WAS ADDED TO PLAN
 THAT STATES TVSS AND SURGE ARRESTOR UNITS SHALL BE NEMA
 3R. THIS DOES NOT ADDRESS PANEL MDP. PROVIDE CORRECTION
 AS PREVIOUSLY REQUESTED.)
 9. CORRECTED.
 10. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE FOR THE BACK AREAS
 INCLUDING THE KITCHEN, OFFICE, AND MULTI-PURPOSE ROOM.
 FBC EC C405.2 (COMMENT RESPONSE STATED THAT EXPLANATION
 FOR LIGHTING CONTROL PANEL WAS ON SHEET E2.2. I FOUND
 NO EXPLANATION OF THIS PANEL AND WHAT IT DOES OR DOES
 NOT CONTROL. PROVIDE AS PREVIOUSLY REQUESTED.)
 11. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  