| 2018-05-18 10:55:56 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. SEVERAL LOCATIONS ON PLAN SHOW THE NEC USED FOR |
| | DESIGN AS OLDER CODES. THE CURRENT NEC IN EFFECT IS THE |
| | 2014 NEC. REMOVE ALL REFERENCES TO OLDER VERSIONS OF |
| | THE CODE. FBC PREFACE, 107.2.1 (SHEET T-1.1 STILL SHOWS |
| | THE 2011 NEC AS BASIS FOR DESIGN. PROVIDE CORRECTION.) |
| | 2. CORRECTED. |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE, |
| | AND FOR PROPER MARKING OF EQUIPMENT PER CODE. NEC |
| | 110.9, 110.10, 110.16, 110.24 (THIS WILL BE A DEFERRED |
| | SUBMITTAL AS DISCUSSED AND WILL SHOW AS A PROVISO ON |
| | PLAN. NO FURTHER ACTION NECESSARY AT THIS TIME.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED, NOT APPLICABLE. |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 (NOTE ADDED TO PLAN |
| | STATES: "INTERLOCK COMMUNICATION SYSTEM GROUND WITH |
| | MAIN GROUND SYSTEM." THIS DOES NOT FULFILL THE |
| | REQUIREMENT PER CODE. AN INTERSYSTEM BONDING |
| | TERMINATION POINT MUST BE LOCATED AT THE SERVICE. SEE |
| | 250.94) |
| | 8. IT APPEARS THE 1200 AMP SERVICE IS LOCATED OUTSIDE. |
| | PROVIDE DETAILS OF ENCLOSURE RATING FOR THIS |
| | ENVIRONMENT. NEC 110.3, 110.28 (NOTE WAS ADDED TO PLAN |
| | THAT STATES TVSS AND SURGE ARRESTOR UNITS SHALL BE NEMA |
| | 3R. THIS DOES NOT ADDRESS PANEL MDP. PROVIDE CORRECTION |
| | AS PREVIOUSLY REQUESTED.) |
| | 9. CORRECTED. |
| | 10. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE FOR THE BACK AREAS |
| | INCLUDING THE KITCHEN, OFFICE, AND MULTI-PURPOSE ROOM. |
| | FBC EC C405.2 (COMMENT RESPONSE STATED THAT EXPLANATION |
| | FOR LIGHTING CONTROL PANEL WAS ON SHEET E2.2. I FOUND |
| | NO EXPLANATION OF THIS PANEL AND WHAT IT DOES OR DOES |
| | NOT CONTROL. PROVIDE AS PREVIOUSLY REQUESTED.) |
| | 11. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |