| 2018-03-17 11:14:16 | 03/17/2018 1ST REVIEW DENIED |
| | 2017 FBC- PLUMBING PLAN REVIEW |
| | W. P. B. PERMIT: 18020060 |
| | |
| | 1. 2018 PERMIT MUST REFLECT THE FLORIDA BUILDING CODE |
| | PLUMBING 2017 6TH EDITION, PLEASE MAKE CHANGES ALONG |
| | WITH ALL OTHER DISCIPLINES WHO HAVE NOTED IT. |
| | 2. A SEPARATE BACKFLOW APPLICATION SHALL BE REQUIRED |
| | AND LOCATION OF THE DEVICE IS SET BY THE WEST PALM |
| | BEACH UTILITIES CROSS CONNECTION MANUAL AND OR |
| | ORDINANCES. |
| | 3. VERTICAL HANDRAIL NOT REQUIRED FOR ADA COMPLIANCE ON |
| | A5.1 |
| | 4. MEN?S ROOM ADA BACK BAR DIMENSION MISSING ON THE |
| | VERTICAL PLANE. WPB AMENDMENTS. TO FBC SEC. 107.2.1. |
| | 5. WHERE IS THE BOOSTER PUMP BEING RELOCATED TO? WPB |
| | AMENDMENTS. TO FBC SEC. 107.2.1. |
| | 6. PIPING ON P-6.1 #2 SHOW A REDUCED PRESSURE VALVE |
| | WATER SERVICE AND YOU ALSO HAVE A BOOSTER PUMP |
| | INCORPORATED IN THE SYSTEM, IS THE RPV REQUIRED? FBC P |
| | SEC. 604.8 WATER PRESSURE-REDUCING VALVE OR REGULATOR. |
| | 7. P-2.1 NOTE 2 AND 4 CALLS FOR PVC WATER DISTRIBUTION |
| | AND IT IS NOT ALLOWED BY PLUMBING CODE ON TABLE FBC P |
| | TABLE 605.4 |
| | 8. NEED SPECIFICATION ON PREFABRICATED BACKFLOW PANEL. |
| | WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | 9. TEMPERED WATER VALVE MUST BE RATED FOR MULTI-LAVS |
| | CAPACITY PER MANUFACTURES SPECIFICATION. |
| | 10. PAGE P2.1 PIPING FOR FILTER NEED SHUT OFF VALVE FOR |
| | TRAP PRIMER AND TO BE CONNECTED BEHIND FULL PORT VALVE |
| | TO ISOLATE, IF THIS A GENERIC AND IT SHOWS THIS WAY |
| | PLEASE CLARIFY IT OR REMOVE IT FOR IT NOT TO CREATE |
| | CONFUSION IN THE FIELD. |
| | 11. ALL WATER FEED MUST BE PROTECTED WITH AN IN-LINE |
| | VACUUM BREAKER. 405.1 WATER SUPPLY PROTECTION. THE |
| | SUPPLY LINES AND FITTINGS FOR EVERY PLUMBING FIXTURE |
| | SHALL BE INSTALLED SO AS TO PREVENT BACKFLOW. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | 12. CONDENSATE MATERIAL ON THE ROOF IS PVC AND THIS |
| | MATERIAL IS NOT UV PROTECTED AND PER MANUFACTURES |
| | SPECIFICATION IT CANNOT BE IN THE SUNLIGHT OF UV, |
| | PLEASE TELL US HOW YOU ARE GOING TO PROTECT IT? WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | 13. A SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED |
| | FOR A CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE |
| | COMPLETE PLANS AND GAS RISER THAT REFLECTS THE ENTIRE |
| | SCOPE OF GAS WORK TO BE DONE AT THIS TIME. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | 14. EXPANSION DEVICE NOT SHOWN IN THE ISOMETRIC |
| | DRAWING, WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | 15. MOP SINK NOT LABELED ON ISOMETRIC AND P1.1. MOP |
| | SINK AS MANUFACTURED PLUMBING FIXTURES OR PLUMBING |
| | FIXTURES CONSTRUCTED ON SITE SHALL MEET THE DESIGN |
| | REQUIREMENTS OF ASME A112.19.2/CSA B45.1 OR ASME |
| | A112.19.3/CSA B45.4. 2017 FBC P 405.9 DESIGN AND |
| | INSTALLATION OF PLUMBING FIXTURES. |
| | 16. PLEASE PROVIDE A SIZING CALCULATION FOR EXISTING |
| | GREASE TRAP TO REFLECT NEW OCCUPANCY LOAD WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | 17. TRAP SEAL SUBJECT TO EVAPORATION SHALL BE |
| | PROTECTED, A BARRIER DEVICE MAY BE USED THAT COMPLIES |
| | WITH ASSE 1072 BUT WHERE FOOD PREPARATION IS PRESENT |
| | THIS DEVICE MAY NOT COMPLY AND A TRAP PRIMER MAY BE |
| | REQUIRED FBC P SEC. 1002.4. PLEASE SUBMIT THE |
| | SPECIFICATION FOR APPROVAL AND REFER TO P-7.1, COMMENT |
| | P26A TO REFLECT THIS ASSE 1072 STANDARD. |
| | 18. REQUIRED PAN DRAIN ON WATER HEATER, SHOW RELIEF |
| | LINE DUMPING INTO PAN DRAIN 2017 FBC P SEC. 504.6 AND |
| | 2017 FBC P SEC. 504.7.1 |
| | 19. ICE MAKER, SOAP OR CHEMICAL DISPENSER SHALL HAVE AN |
| | INLINE BACKFLOW DEVICE AND THE SODA DISPENSER SHALL |
| | HAVE A CARBONATED BACKFLOW DEVICE AS WELL. EACH DEVICE |
| | SHALL HAVE ITS OWN SHUT-OFF VALVE FBC P SEC. 608.13.9 |
| | CHEMICAL DISPENSER BACKFLOW DEVICES, 608.16.7 CHEMICAL |
| | DISPENSERS, 608.16.1 BEVERAGE DISPENSERS. |
| | 20. ISOMETRIC OF THE SANITARY RISER ON P-5.1, (N)P-6 |
| | THE DIRECTION OF FLOW IS INCORRECT. WPB AMENDMENTS TO |
| | FBC SEC. 107.2.1. |
| | |
| | |
| | PLEASE NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE |
| | AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | [email protected] |
| | 561-805-6720 |
| | |
| | |