Plan Review Notes
Plan Review Notes For Permit 18020060
Permit Number 18020060
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-17 11:14:1603/17/2018 1ST REVIEW DENIED
 2017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 18020060
  
 1. 2018 PERMIT MUST REFLECT THE FLORIDA BUILDING CODE
 PLUMBING 2017 6TH EDITION, PLEASE MAKE CHANGES ALONG
 WITH ALL OTHER DISCIPLINES WHO HAVE NOTED IT.
 2. A SEPARATE BACKFLOW APPLICATION SHALL BE REQUIRED
 AND LOCATION OF THE DEVICE IS SET BY THE WEST PALM
 BEACH UTILITIES CROSS CONNECTION MANUAL AND OR
 ORDINANCES.
 3. VERTICAL HANDRAIL NOT REQUIRED FOR ADA COMPLIANCE ON
 A5.1
 4. MEN?S ROOM ADA BACK BAR DIMENSION MISSING ON THE
 VERTICAL PLANE. WPB AMENDMENTS. TO FBC SEC. 107.2.1.
 5. WHERE IS THE BOOSTER PUMP BEING RELOCATED TO? WPB
 AMENDMENTS. TO FBC SEC. 107.2.1.
 6. PIPING ON P-6.1 #2 SHOW A REDUCED PRESSURE VALVE
 WATER SERVICE AND YOU ALSO HAVE A BOOSTER PUMP
 INCORPORATED IN THE SYSTEM, IS THE RPV REQUIRED? FBC P
 SEC. 604.8 WATER PRESSURE-REDUCING VALVE OR REGULATOR.
 7. P-2.1 NOTE 2 AND 4 CALLS FOR PVC WATER DISTRIBUTION
 AND IT IS NOT ALLOWED BY PLUMBING CODE ON TABLE FBC P
 TABLE 605.4
 8. NEED SPECIFICATION ON PREFABRICATED BACKFLOW PANEL.
 WPB AMENDMENTS TO FBC SEC. 107.2.1.
 9. TEMPERED WATER VALVE MUST BE RATED FOR MULTI-LAVS
 CAPACITY PER MANUFACTURES SPECIFICATION.
 10. PAGE P2.1 PIPING FOR FILTER NEED SHUT OFF VALVE FOR
 TRAP PRIMER AND TO BE CONNECTED BEHIND FULL PORT VALVE
 TO ISOLATE, IF THIS A GENERIC AND IT SHOWS THIS WAY
 PLEASE CLARIFY IT OR REMOVE IT FOR IT NOT TO CREATE
 CONFUSION IN THE FIELD.
 11. ALL WATER FEED MUST BE PROTECTED WITH AN IN-LINE
 VACUUM BREAKER. 405.1 WATER SUPPLY PROTECTION. THE
 SUPPLY LINES AND FITTINGS FOR EVERY PLUMBING FIXTURE
 SHALL BE INSTALLED SO AS TO PREVENT BACKFLOW. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 12. CONDENSATE MATERIAL ON THE ROOF IS PVC AND THIS
 MATERIAL IS NOT UV PROTECTED AND PER MANUFACTURES
 SPECIFICATION IT CANNOT BE IN THE SUNLIGHT OF UV,
 PLEASE TELL US HOW YOU ARE GOING TO PROTECT IT? WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 13. A SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED
 FOR A CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE AT THIS TIME. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 14. EXPANSION DEVICE NOT SHOWN IN THE ISOMETRIC
 DRAWING, WPB AMENDMENTS TO FBC SEC. 107.2.1.
 15. MOP SINK NOT LABELED ON ISOMETRIC AND P1.1. MOP
 SINK AS MANUFACTURED PLUMBING FIXTURES OR PLUMBING
 FIXTURES CONSTRUCTED ON SITE SHALL MEET THE DESIGN
 REQUIREMENTS OF ASME A112.19.2/CSA B45.1 OR ASME
 A112.19.3/CSA B45.4. 2017 FBC P 405.9 DESIGN AND
 INSTALLATION OF PLUMBING FIXTURES.
 16. PLEASE PROVIDE A SIZING CALCULATION FOR EXISTING
 GREASE TRAP TO REFLECT NEW OCCUPANCY LOAD WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 17. TRAP SEAL SUBJECT TO EVAPORATION SHALL BE
 PROTECTED, A BARRIER DEVICE MAY BE USED THAT COMPLIES
 WITH ASSE 1072 BUT WHERE FOOD PREPARATION IS PRESENT
 THIS DEVICE MAY NOT COMPLY AND A TRAP PRIMER MAY BE
 REQUIRED FBC P SEC. 1002.4. PLEASE SUBMIT THE
 SPECIFICATION FOR APPROVAL AND REFER TO P-7.1, COMMENT
 P26A TO REFLECT THIS ASSE 1072 STANDARD.
 18. REQUIRED PAN DRAIN ON WATER HEATER, SHOW RELIEF
 LINE DUMPING INTO PAN DRAIN 2017 FBC P SEC. 504.6 AND
 2017 FBC P SEC. 504.7.1
 19. ICE MAKER, SOAP OR CHEMICAL DISPENSER SHALL HAVE AN
 INLINE BACKFLOW DEVICE AND THE SODA DISPENSER SHALL
 HAVE A CARBONATED BACKFLOW DEVICE AS WELL. EACH DEVICE
 SHALL HAVE ITS OWN SHUT-OFF VALVE FBC P SEC. 608.13.9
 CHEMICAL DISPENSER BACKFLOW DEVICES, 608.16.7 CHEMICAL
 DISPENSERS, 608.16.1 BEVERAGE DISPENSERS.
 20. ISOMETRIC OF THE SANITARY RISER ON P-5.1, (N)P-6
 THE DIRECTION OF FLOW IS INCORRECT. WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
  
  
 PLEASE NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE
 AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  