| Date |
Text |
| 2018-03-06 17:39:53 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION, |
| | WEST PALM BEACH AMENDMENTS TO THE FBC. |
| | PERMIT #18020060 |
| | 3/6/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR: A) |
| | KITCHEN HOODS AND EXHAUST SYSTEMS. B) FIRE SUPPRESSION |
| | SYSTEMS. C) WALK-IN COOLERS AND FREEZERS. PLEASE PLACE |
| | A NOTE ON THE PLAN IN BOLD LETTERS. |
| | |
| | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS SECTION C403.2.1 FBC-17 ENERGY CONSERVATION. |
| | |
| | 3) SHEET M-1.1: PROVIDE DUCT SMOKE DETECTORS IN THE |
| | SUPPLY SYSTEMS OF AC #2 & #3- SECTION 606.2.1. |
| | |
| | 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF ALL ROOFTOP EQUIPMENT, AND THE REQUIRED CLEARANCE |
| | DISTANCE MEASUREMENTS FROM AIR INTAKES TO EXHAUST |
| | OUTLETS- SECTION 107.1 WPB AMENDMENTS. |
| | |
| | 5) M-3.1: REFER TO SECTION C403.2.8 AND SHOW COMPLIANCE |
| | IN THE PLANS AND CALCULATIONS- C403.2.8 KITCHEN EXHAUST |
| | SYSTEMS: |
| | |
| | REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST |
| | HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE |
| | HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR |
| | DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF |
| | THE FOLLOWING: |
| | |
| | 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE |
| | HEATING OR COOLING LOAD. |
| | |
| | 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER |
| | AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS |
| | CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT |
| | REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS |
| | RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION |
| | OF ADJACENT SPACES. |
| | |
| | WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS |
| | GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A |
| | FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE |
| | WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST |
| | RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | |
| | 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL |
| | BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED. |
| | |
| | 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75 |
| | PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS |
| | THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT |
| | AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY |
| | TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION |
| | AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE, |
| | EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND |
| | IDLE. |
| | |
| | 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT |
| | RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON |
| | NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW. |
| | |
| | WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER |
| | APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM |
| | ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL |
| | BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE |
| | DUTY RATING UNDER THE HOOD OR HOOD SECTION. |
| | |
| | EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE |
| | REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE |
| | EXHAUSTED |
| | |
| | 6) M-4.1: PROVIDE COMPLETE WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF THE NEW AND RELOCATED RTU'S INCLUDING |
| | THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE WITH |
| | SECTION 1609 FBC-17 BUILDING. INDICATE HOW THE UNIT |
| | CURBS WILL BE ATTACHED TO THE ROOF STRUCTURE AND HOW |
| | THE RTU'S AND FANS WILL BE ATTACHED TO THE CURBS- |
| | SECTION 301.15. |
| | |
| | 7) M-4.2: PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE |
| | NOA FOR THE AVCOA CONDENSER STAND WITH REVIEW STAMP BY |
| | THE ENGINEER OF RECORD. THE EOR SHALL CIRCLE, |
| | HIGHLIGHT, OR OTHERWISE MARK ALL APPLICABLE |
| | INSTALLATION DETAILS AND DESIGN PRESSURES SHOWN IN THE |
| | DOCUMENT- SECTION 301.15. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |