Plan Review Notes
Plan Review Notes For Permit 18020060
Permit Number 18020060
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-06 17:39:531ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION,
 WEST PALM BEACH AMENDMENTS TO THE FBC.
 PERMIT #18020060
 3/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR: A)
 KITCHEN HOODS AND EXHAUST SYSTEMS. B) FIRE SUPPRESSION
 SYSTEMS. C) WALK-IN COOLERS AND FREEZERS. PLEASE PLACE
 A NOTE ON THE PLAN IN BOLD LETTERS.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
  
 3) SHEET M-1.1: PROVIDE DUCT SMOKE DETECTORS IN THE
 SUPPLY SYSTEMS OF AC #2 & #3- SECTION 606.2.1.
  
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOFTOP EQUIPMENT, AND THE REQUIRED CLEARANCE
 DISTANCE MEASUREMENTS FROM AIR INTAKES TO EXHAUST
 OUTLETS- SECTION 107.1 WPB AMENDMENTS.
  
 5) M-3.1: REFER TO SECTION C403.2.8 AND SHOW COMPLIANCE
 IN THE PLANS AND CALCULATIONS- C403.2.8 KITCHEN EXHAUST
 SYSTEMS:
  
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
  
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
  
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
  
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
  
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED
  
 6) M-4.1: PROVIDE COMPLETE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE NEW AND RELOCATED RTU'S INCLUDING
 THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE WITH
 SECTION 1609 FBC-17 BUILDING. INDICATE HOW THE UNIT
 CURBS WILL BE ATTACHED TO THE ROOF STRUCTURE AND HOW
 THE RTU'S AND FANS WILL BE ATTACHED TO THE CURBS-
 SECTION 301.15.
  
 7) M-4.2: PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE AVCOA CONDENSER STAND WITH REVIEW STAMP BY
 THE ENGINEER OF RECORD. THE EOR SHALL CIRCLE,
 HIGHLIGHT, OR OTHERWISE MARK ALL APPLICABLE
 INSTALLATION DETAILS AND DESIGN PRESSURES SHOWN IN THE
 DOCUMENT- SECTION 301.15.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER