| 2018-03-07 15:49:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SEVERAL LOCATIONS ON PLAN SHOW THE NEC USED FOR |
| | DESIGN AS OLDER CODES. THE CURRENT NEC IN EFFECT IS THE |
| | 2014 NEC. REMOVE ALL REFERENCES TO OLDER VERSIONS OF |
| | THE CODE. FBC PREFACE, 107.2.1 |
| | 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. FBC 105.1, 107.2.1 |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE, |
| | AND FOR PROPER MARKING OF EQUIPMENT PER CODE. NEC |
| | 110.9, 110.10, 110.16, 110.24 |
| | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 5. MAIN BONDING JUMPER IS SIZED AS 3/0 COPPER, WHICH IS |
| | TOO SMALL. THIS WIRE SHOULD BE SIZED A MINIMUM OF 12.5% |
| | OF THE SERVICE CONDUCTOR TOTAL AREA. PROVIDE |
| | CORRECTION. NEC 250.28(D), TABLE 250.102(C)(1) |
| | 6. SHOW COMPLIANCE WITH NEC 240.87 |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 8. IT APPEARS THE 1200 AMP SERVICE IS LOCATED OUTSIDE. |
| | PROVIDE DETAILS OF ENCLOSURE RATING FOR THIS |
| | ENVIRONMENT. NEC 110.3, 110.28 |
| | 9. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 10. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE FOR THE BACK AREAS |
| | INCLUDING THE KITCHEN, OFFICE, AND MULTI-PURPOSE ROOM. |
| | FBC EC C405.2 |
| | 11. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: ?WITHIN |
| | 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO |
| | THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM |
| | OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. |
| | FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL |
| | DISTRIBUTION.? FBC EC C405.6.4.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |