Plan Review Notes
Plan Review Notes For Permit 18020060
Permit Number 18020060
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-02 17:13:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020060
 ADD: 2020 PALM BEACH LAKES BLVD. SUITE:2070
 CONT: TBD/ TO BE DETERMINED
 TEL: 407-629-9124
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 02/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET T-I.I:
 1A) PLEASE NOTE THE PLANS WERE SIGNED AND SEALED ON
 DEC. 14/ 2017 AND DESIGNED UNDER THE 2014 FBC BUT THEY
 WERE SUBMITTED ON FEB. 02/2018. DEC.31/2017 THE 6TH
 EDITION OR 2017 FBC FAMILY OF CODES WAS ADOPTED
 STATEWIDE. PLEASE REVIEW THE DIFFERENCE IN CODES, PLANS
 NEED TO SHOW CODE COMPLIANCE TO THE 2017 FBC.
  
 1B) ON THE LEFT SIDE OF THE SHEET JUST ABOVE THE AREA
 MAP THERE IS A STATEMENT THAT THIS PROJECT IS A LEVEL 2
 ALTERATION AND ADDITION AS DEFINED BY THE INTERNATIONAL
 BUILDING CODE. PLEASE NOTE THE IBC MAYBE THE BASE CODE,
 BUT THE 2017 FLORIDA BUILDING CODE, EXISTING BUILDING
 IS THE CODE ADOPTED STATEWIDE, PLEASE CORRECT THE CODE
 REFERENCE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1C) THE COVERSHEET NOTE 11.3 INDICATES THE EXISTING RTU
 # 4 IS TO BE REPLACED WHEREAS SHEET A1.7 AND
 SHEET M-I.I BOTH INDICATE THE 2 UNITS WILL BE REMAINING
 NOT BEING REPLACED? 107.2.1.3 DISCREPANCY IN PLANS,
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-I.I AT THE DRIVE THROUGH WINDOW THERE ARE
 NOTES FOR THE BOND BEAM. SEE A1.3 STRUCTURAL FOR NEW
 BOND BEAM WITH BOTTOM AT 6 FOOT 0 3/8 INCH A.F.F. SHEET
 A-1.3 DETAIL 13 SHOW THE BOTTOM OF THE DRIVE THROUGH
 WINDOW AT 3 FOOT. A-I.I CUT SECTION THROUGH THE DRIVE
 THROUGH WINDOW DETAIL 3/ A3.1 . ON SHEET
 A-3.1 DETAIL 3 SHOWS A CUT SECTION THROUGH THE
 DRIVE-THRU WITH THE BOTTOM OF THE WINDOW AGAIN AT 3
 FOOT A.F.F. IN THIS SAME WALL SECTION OF THE DRIVE THRU
 WINDOW THERE ARE 2 MORE DETAILS OF THE WINDOW SILL
 12/A1.3 AND THE HEADER 11/A1.3 BOTH OF THESE DETAILS
 ARE ALSO MISLABELED. PLEASE CORRECT ALL OF THE
 MISLABELED DETAILS AND OR SECTIONS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) THE COVERSHEET NOTE # 7 INDICATES SEE ASP-I.I AND
 LANE CANOPIES SHOP DRAWINGS FOR NEW CANOPY LAYOUT.
 PLEASE NOTE SHEET ASP-I.I IS JUST A LAYOUT SHEET
 SHOWING THE DIMENSION. THERE IS NO INFORMATION AS TO
 THE CANOPY, MATERIALS, SIZE OF FRAMING MEMBERS, GAUGE
 OF METAL, DECKING MATERIAL NOR IS THERE ANY SHOP
 DRAWINGS.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES.
  
 CANOPY DRAWINGS (SHOP DRAWINGS) CAN BE A DEFERRED
 SUBMITTAL. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4) SHEET A-1.3 DETAILS 14 & 15 BOTH INDICATE THE USE OF
 CMU FOAM INSULATION AND REFERENCE 6A3.1. THE INDEX
 SHEET DOES NOT REFERENCE A 6A3.1? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 5) UNDER THE 1ST REVIEW THERE WERE NO DOCUMENTS
 SUBMITTED FOR COMPLIANCE WITH THE ENERGY CODE. THERE
 ARE 2 CRITERIA THAT NEEDS TO BE DETERMINED:
  
 5A) IF THIS BUILDING MEETS THE DEFINITION OF RENOVATED
 BUILDING UNDER THE 2017 FBC-ENERGY CODE.
 RENOVATED BUILDING. A RESIDENTIAL OR NONRESIDENTIAL
 BUILDING UNDERGOING ALTERATION THAT VARIES OR CHANGES
 INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS OR
 EXTERIOR ENVELOPE CONDITIONS, PROVIDED THE ESTIMATED
 COST OF RENOVATION EXCEEDS 30 PERCENT OF THE ASSESSED
 VALUE OF THE STRUCTURE.
  
 5B) 2017 FBC-ENERGY CODE C401.2 APPLICATION. COMMERCIAL
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL
 COMPLY WITH SECTION C406 AND TENANT SPACES SHALL COMPLY
 WITH SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407.
 THE BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN
 85 PERCENT OF THE STANDARD REFERENCE
 DESIGN BUILDING.
  
 6) SHEET S0.1:
 6A) SHEET S0.1 INDICATES UNDER NOTE # 2 THE DESIGN AND
 CONSTRUCTION SHALL BE BASED ON THE 2014 FBC-B. THE
 PLANS WERE SIGNED AND DATED 12/15/2017. THE PLANS WERE
 SUBMITTED ON FEB. 02/2018. DEC.31/2017 THE 6TH EDITION
 OR 2017 FBC FAMILY OF CODES WAS ADOPTED STATEWIDE.
 PLEASE REVIEW THE DIFFERENCE IN CODES, PLANS NEED TO
 SHOW THE BUILDING DESIGN IS BASED ON THE 2017 FBC
 ?BUILDING, THE 6TH EDITION OF THE FLORIDA BUILDING
 CODE.
  
 6B) THE FOUNDATION NOTES 1 & 2 BOTH APPEAR THERE SHOULD
 BE A SOILS REPORT SUBMITTED BASED ON AN ALLOWABLE SOILS
 BEARING PRESSURE OF 2000 PSF AND TO BE CONFIRMED BY A
 FLORIDA LICENSED SOILS ENGINEER.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL.
  
 6C) NOTICE ONLY NOT NECESSARY FOR A RESPONSE. THE ROOF
 PRESSURES AND WALL PRESSURES SUBMITTED IN VASD ARE ALL
 GOOD!
  
 6D) NOTES UNDER THE HEADING MASONRY WALL CONSTRUCTION
 NOTE 10 FOR LINTELS INDICATES SUBMIT SHOP DRAWINGS WITH
 RATED LOAD CAPACITIES. TO BE REVIEWED BY THE STRUCTURAL
 ENGINEER OF RECORD AND SHOP DRAWING STAMP OF APPROVAL
 APPLIED BEFORE BEING SUBMITTED TO THE JURISDICTION
 HAVING AUTHORITY.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 7) PLEASE SUBMIT PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 FANS, VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS & LINTELS
  
 7A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 9) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 10 ) SHEET A-5.3 DETAIL #4 SHOWS THE FRONT SERVING
 COUNTER BUT THERE ARE NO MEASUREMENTS PROVIDING
 COMPLIANCE WITH ACCESSIBILITY.
 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE
 LINES SHALL COMPLY WITH 904.5.
  
 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
  
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 11) SHEET A-1.1 SHOWS THE REQUIRED AMOUNT OF ACCESSIBLE
 TABLES, WHAT THE PLAN DOES NOT SHOW IS AT WHAT HEIGHT
 THE ACCESSIBLE TABLE ARE FROM THE FINISH FLOOR AND
 COMPLIANCE WITH;
 2017 FBC- ACCESSIBILITY CODE SECTION 902.3 HEIGHT. THE
 TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 12) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676