2018-05-10 11:24:133RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020058
 5/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED LETTER FROM KAMM ENGINEERING IS
 ADDRESSING PRESSURIZATION OF THE SPACES RATHER THAN THE
 ISSUE OF TEMPERSATURE OF MAKEUP AIR. PLEASE NOTE THAT
 IF USING THE EXCEPTION IN 508.1.1 THAT THE ADDED
 COOLING LOAD FROM THE MAKEUP AIR DOES NOT EXCEED THE
 CAPACITY OF THE AC SYSTEM, PLEASE STATE THAT CLEARLY IN
 THE LETTER AND PROVIDE CALCULATIONS TO SHOW COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER