| 2018-04-03 11:26:41 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18020058 |
| | 4/3/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE LETTER FROM KAMM ENGINEERING THAT WAS SIGNED BY |
| | THE PROJECT MANAGER JOHN MAYR DOES NOT ADDRESS COMMENT |
| | #1 FROM THE 1ST REVIEW. THE SUBMITTED LETTER MAKES THIS |
| | GENERAL STATEMENT " THE HOOD SYSTEM HAS BEEN TAKEN INTO |
| | ACCOUNT DURING THE DESIGN OF THE BUILDING HVAC SYSTEM". |
| | HOWEVER NO EVIDENCE IN THE FORM OF CALCULATIONS, DATA, |
| | OR EXPLANATORY INFORMATION HAS BEEN PROVIDED TO SHOW |
| | THE ADDED COOLING LOAD OF THE MAKEUP AIR HAS BEEN |
| | CALCULATED INTO THE TOTAL DESIGN LOADS FOR SIZING OF |
| | THE HVAC SYSTEMS. PLEASE NOTE THAT GENERALLY ABOUT 20% |
| | OF THE SUPPLY AIR PROVIDED FOR THE HOOD IS DIFFUSED |
| | INTO THE SPACE. THAT IS THE BASIS OF THE REQUIRED |
| | CALCULATION. I HAVE REPRINTED THE COMMENT BELOW- PLEASE |
| | SHOW COMPLIANCE. |
| | |
| | 1) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR |
| | TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL |
| | NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |