Plan Review Notes
Plan Review Notes For Permit 18020058
Permit Number 18020058
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-03 11:26:412ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18020058
 4/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LETTER FROM KAMM ENGINEERING THAT WAS SIGNED BY
 THE PROJECT MANAGER JOHN MAYR DOES NOT ADDRESS COMMENT
 #1 FROM THE 1ST REVIEW. THE SUBMITTED LETTER MAKES THIS
 GENERAL STATEMENT " THE HOOD SYSTEM HAS BEEN TAKEN INTO
 ACCOUNT DURING THE DESIGN OF THE BUILDING HVAC SYSTEM".
 HOWEVER NO EVIDENCE IN THE FORM OF CALCULATIONS, DATA,
 OR EXPLANATORY INFORMATION HAS BEEN PROVIDED TO SHOW
 THE ADDED COOLING LOAD OF THE MAKEUP AIR HAS BEEN
 CALCULATED INTO THE TOTAL DESIGN LOADS FOR SIZING OF
 THE HVAC SYSTEMS. PLEASE NOTE THAT GENERALLY ABOUT 20%
 OF THE SUPPLY AIR PROVIDED FOR THE HOOD IS DIFFUSED
 INTO THE SPACE. THAT IS THE BASIS OF THE REQUIRED
 CALCULATION. I HAVE REPRINTED THE COMMENT BELOW- PLEASE
 SHOW COMPLIANCE.
  
 1) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  