2018-02-13 15:07:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18020058
 2/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10?F (6?C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 2) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP FANS- SEE SECTION 1609
 FBC-17 BUILDING.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DUCT
 WRAP WITH SHOP DRAWING STAMP BY THE EOR- SECTION
 506.3.11.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  