| 2018-02-02 13:19:49 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) THERE IS NO CLEAR INDICATION OF A MANUAL PULL | | | STATION FOR THE SYSTEM. PLEASE ENSURE ONE IS INSTALLED | | | PER NFPA 96: | | | | | | 10.5 MANUAL ACTIVATION. | | | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION | | | SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. | | | AND 48 IN.) ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT | | | OF A FIRE, BE LOCATED IN A PATH OF EGRESS, AND CLEARLY | | | IDENTIFY THE HAZARD PROTECTED. | | | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE | | | LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M | | | (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) | | | WITHIN A PATH OF EGRESS OR AT AN ALTERNATIVE LOCATION | | | ACCEPTABLE TO THE AHJ. | | | 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL | | | STATION SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF | | | FORCE, WITH A PULL MOVEMENT NOT TO EXCEED 356 MM (14 | | | IN.) TO ACTIVATE THE AUTOMATIC FIRE-EXTINGUISHING | | | EQUIPMENT. | | | | | | | | | | | | 2) ENSURE THAT A FIRE ALARM TECH IS ON SITE WHEN THE | | | FIRE INSPETION TEST IS SCHEDULED. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|