2018-02-07 06:40:37DENIED
  
 PLUMBING REPAIR TUNNEL WORK
  
 A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE
 SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO
 EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED,
 THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO
 EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS.
 DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED
 THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE
 CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND
 BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW
 GROUND PER THE 2017 FLORIDA BUILDING CODE, RESIDENTIAL,
 SECTION 318.8 AND THE 2017 FLORIDA BUILDING CODE,
 BUILDING, SECTION 2603.9.
 A SIGNED AND SEALED LETTER FROM AN ENGINEER MAY BE
 REQUIRED TO CERTIFY THE STRUCTURAL INTEGRITY OF THE
 EXISTING SLAB.
 THE BACKFILL UNDER THE SLAB SHALL BE TREATED FOR
 TERMITES PER THE 2017 FBC B SEC.1816.1 OR 2017 FBC R
 SEC. 318.1. A TERMITE CERTIFICATE SHALL BE ONSITE FOR
 FINAL INSPECTION.
  