Plan Review Notes
Plan Review Notes For Permit 18020031
Permit Number 18020031
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-07 11:43:201ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL, ENERGY
 CONSERVATION CODES
 PERMIT #18020031
 2/7/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CONTRACTOR MUST PROVIDE HIS SIGNATURE AND DATE
 ON THE PLAN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 2) SHOW THE LOCATION AND DIMENSIONS OF THE REQUIRED
 ATTIC HATCH TO ACCESS THE AIR HANDLER- SEE SECTION
 R403.3.6 FBC-17 ENERGY CONSERVATION FOR ALL
 REQUIREMENTS.
  
 3) PROVIDE A CONDENSATE DISPOSAL PLAN THAT SHOWS THE
 TYPE AND SIZE OF PIPING, AND THE PIPING RUN AND
 DISCHARGE LOCATION- M1411.3 FBC-17 RESIDENTIAL.
  
 4) ENLARGE THE HURRICAN PAD SUBMITTAL AND INDICATE THE
 PAD MODEL NUMBER AND DIMENSIONS OF THE PAD. SUBMIT A
 FL. PRODUCT APPROVAL FOR THE TIE DOWN CLIPS.
  
 5) AC CALCULATIONS PROJECT SUMMARY: PROVIDE THE MAKE
 AND MODEL OF THE THE CONDENSER AND AIR HANDLER IN THE
 COOLING EQUIPMENT SUMMARY- SECTION R403.7.1 FBC-17
 ENERGY CONSERVATION.
  
 6) THE OWNER/AGENT MUST PROVIDE HIS/HER SIGNATURE ON
 THE ENERGY COMPLIANCE FORM R405-2017.
  
 7) ADVISORY: PLEASE REVIEW THE REQUIRED COMPLIANCE
 TESTS LISTED AT THE BOTTOM OF PAGE 1 OF FORM R405-2017.
 MANDATORY ENVELOPE AND DUCT LEAKAGE TESTS REQUIRED FOR
 COMPLIANCE WITH R405-2017.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved