| 2018-03-20 12:06:37 | 1) THE SUBMITTED GAS PLAN IS A COPY OF A SIGNED AND |
| | SEALED PLAN BY AN ENGINEER.PLANS BEARING AND ENGINEER'S |
| | TITLE BLOCK SHALL ALSO HAVE AN ORIGINAL SIGNATURE AND |
| | SEAL PER THE FL. ADMIN. CODE 61G15-23.001. SUBMIT TWO |
| | COPIES OF THE GAS PLAN BEARING THE ORIGINAL SEAL AND |
| | SIGNATURE OF THE ENGINEER. |
| | 2) SHOW THE LOCATION OF THE METAL LOUVERS THAT ARE |
| | BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS |
| | CANNOT BE LOCATED IN AN EXTERIOR WALL THAT IS FIRE |
| | RATED AS THE FIRE RATING OF THE WALL MUST BE |
| | MAINTAINED. |
| | 3) THE LOUVERS ARE NOT PERMITTED IN AN EXTERIOR WALL |
| | WITH A FIRE SEPARATION DISTANCE, TYPE OF CONSTRUCTION, |
| | AND WHETHER OR NOT THE BUILDING IS SPRINKLERED AS |
| | LISTED IN TABLE 705.8 OF 2017 FBC-BUILDING.SUBMIT ALL |
| | REQUIRED INFORMATION. SUBMIT A SITE PLAN SHOWING THE |
| | DISTANCE OF ALL EXTERIOR WALLS TO ADJACENT PROPERTY |
| | LINES. WPB AMEND. TO FBC SEC.107.2.1. |
| | 4) SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS. |
| | 5) THIS PLAN SHALL BE TAKEN TO THE ENGINEER OF RECORD |
| | TO BE SIGNED AND SEALED AND SUBMITTED AS CORRECTIONS |
| | ALONG WITH ALL OTHER CORRECTIONS UNDER THE MASTER |
| | PERMIT NUMBER 18020521. THIS GAS PERMIT CANNOT BE |
| | ISSUED UNTIL THE MASTER PERMIT HAS BEEN APPROVED. |
| | 6) COPIES OF EQUIPMENT SPECIFICATIONS HAVE BEEN |
| | SUBMITTED FOR TWO DIFFERENT PIECES OF EQUIPMENT BY TWO |
| | DIFFERENT MANUFACTURERS. THE PLANS SHOW A ROTATING RACK |
| | OVEN BUT SPECS HAVE ALSO BEEN PROVIDED FOR A DOUBLE |
| | RACK OVEN. WHICH ONE IS BEING INSTALLED? CLARIFY. |
| | |
| | TIM LARGE |