| 2018-05-10 16:30:42 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18020006 |
| | 5/10/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE USE OF THE KINGSPAN 300 INSULATED WALL PANELS TO |
| | FORM THE ROOF OF THE WALK-IN COOLER IS STILL IN |
| | QUESTION BY THE BUILDING DEPARTMENT. AS PREVIOUSLY |
| | STATED IN THE1ST AND 2ND REVIEWS, THE ENGINEERING |
| | REPORT CONTAINED IN THE MIAMI-DADE NOA #16-0706.08 |
| | INDICATES THE PANELS HAVE BEEN EVALUATED AS NON BEARING |
| | EXTERIOR WALL PANELS. THEY HAVE NOT BEEN EVALUATED AS A |
| | ROOF |
| | |
| | PANEL. IN RESPONSE, THE PROJECT MANAGER HAS SUBMITTED A |
| | DOCUMENT FROM THE MANUFACTURER TITLED "UNIFORM WIND + |
| | THERMAL LOAD". THIS STRUCTURAL ANALYSIS APPEARS TO BE |
| | FOR AN INDIVIDUAL WALL PANEL, AND DOES NOT ADDRESS THE |
| | USE OF THE PANEL AS A ROOF PANEL. FURTHER, THE ANALYSIS |
| | IS NOT SITE SPECIFIC AND IS NOT SIGNED AND SEALED BY A |
| | FLORIDA REGISTERED ENGINEER AS REQUIRED BY FLORIDA |
| | |
| | STAUTE 471, AND FAC 16G15-23.002. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |