| 2018-03-14 18:02:37 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #18020006 |
| | 3/14/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. I HAVE |
| | REPRINTED IT BELOW WITH SOME ADDITIONAL INFORMATION: |
| | |
| | NOA #16-0706.08 PROVIDES ENGINEERING CERTIFICATION FOR |
| | THE THERMALSPAN 300 INSULATED METAL WALL PANELS. THERE |
| | ARE NO DETAILS OR CERTIFICATIONS ON THE NOA FOR THE |
| | ROOF PANELS, AND NO TYPICAL DETAILS ARE PROVIDED FOR |
| | ATTACHMENT AND SUPPORT OF ROOF PANELS. |
| | |
| | PLEASE REFER TO THE ENGINEERING REPORT & DRAWINGS FOR |
| | THE THERMALSPAN 300 INSULATED METAL WALL PANELS |
| | ATTACHED WITH THE NOA. ON PAGE 2 OF THE DOCUMENT SEE |
| | ITEM 3.0 EVALUATED USES, AND 4.0 ASSEMBLY DESCRIPTION. |
| | THE ENGINEER IS CLEARLY STATING THAT THESE PANELS ARE |
| | NON-LOAD BEARING AND CAN ONLY BE INSTALLED VERTICALLY. |
| | THE DRAWING ON PLAN SHEET 2 IS DEPICTING AN |
| | |
| | INSTALLATION INCONSISTENT WITH THE ENGINEERING |
| | CERTIFICATION, AND BEYOND THE LIMITATIONS OF USE FOR |
| | THE PANEL. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |