| Plan Review Notes For Permit 18011283 |
| Permit Number |
18011283 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-07 10:44:28 | 1) THE PIPING SYSTEM SHALL BE SIZED TO MEET THE MAXIMUM | | | DEMAND TO EACH APPLIANCE. 2017 FBC-FUEL GAS SECS. | | | 402.1, 402.2.. THE GAS PLAN SHOWS A BTU LOAD OF 191,000 | | | BTU'S YET THE GENERATOR SPECS SHOW A BTU LOAD OF | | | 300,000 BTU'S AT FULL LOAD. THE GAS SYSTEM SHALL BE | | | SIZED FOR THE 300,000 BTU LOAD. | | | 2) THE GAS PLAN SHOWS A 1/2 LB. PRESSURE GAS SYSTEM BUT | | | THE SUBMITTED SITE PLAN SHOWS A 2 PSI GAS METER. | | | CLARIFY. | | | 3) THE GAS PLAN SHOWS A NATURAL GAS METER AND NOTES A | | | NATURAL GAS SYSTEM, BUT THE PLAN ALSO NOTES AN LP GAS | | | SYSTEM. CLARIFY. | | | 4) IF THIS IS TO BE A 1/2 LB. GAS SYSTEM, THE ENTIRE | | | PIPING SYSTEM IS UNDERSIZED. COMPLY WITH 2017 FBC-FUEL | | | GAS SEC.402.3. | | | 5) THE SUBMITTED GAS TABLES ARE BOTH FOR LESS THAN A 2 | | | PSI SYSTEM, BUT THE SITE PLAN SHOWS A 2 PSI METER. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|