Plan Review Notes
Plan Review Notes For Permit 18011283
Permit Number 18011283
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-07 10:44:281) THE PIPING SYSTEM SHALL BE SIZED TO MEET THE MAXIMUM
 DEMAND TO EACH APPLIANCE. 2017 FBC-FUEL GAS SECS.
 402.1, 402.2.. THE GAS PLAN SHOWS A BTU LOAD OF 191,000
 BTU'S YET THE GENERATOR SPECS SHOW A BTU LOAD OF
 300,000 BTU'S AT FULL LOAD. THE GAS SYSTEM SHALL BE
 SIZED FOR THE 300,000 BTU LOAD.
 2) THE GAS PLAN SHOWS A 1/2 LB. PRESSURE GAS SYSTEM BUT
 THE SUBMITTED SITE PLAN SHOWS A 2 PSI GAS METER.
 CLARIFY.
 3) THE GAS PLAN SHOWS A NATURAL GAS METER AND NOTES A
 NATURAL GAS SYSTEM, BUT THE PLAN ALSO NOTES AN LP GAS
 SYSTEM. CLARIFY.
 4) IF THIS IS TO BE A 1/2 LB. GAS SYSTEM, THE ENTIRE
 PIPING SYSTEM IS UNDERSIZED. COMPLY WITH 2017 FBC-FUEL
 GAS SEC.402.3.
 5) THE SUBMITTED GAS TABLES ARE BOTH FOR LESS THAN A 2
 PSI SYSTEM, BUT THE SITE PLAN SHOWS A 2 PSI METER.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW