| 2018-02-16 07:26:40 | 02/16/2018 GAS 1ST REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) GAS REGULATOR MANUAL PROVIDED IS MISSING PAGES 4-10. |
| | COMPLETE MANUAL IS REQUIRED, 2017 FBC- FUEL GAS 410.1 |
| | |
| | 2) REQUIRED SEDIMENT TRAP FOR THE GENERATOR IS MISSING |
| | ON YOUR ISOMETRIC PLAM AND I WAS UNABLE TO LOCATE ONE |
| | BUILT IN THE GENERATOR FROM THE MANUAL SUPPLIED. 2017 |
| | FBC FUEL GAS 408.4 |
| | |
| | 3) YOUR ISOMETRIC DRAWING LIST THE CORRECT 2017 FBC |
| | FUEL AND GAS CODE BUT THE COPIES OF THE SIZING CHARTS |
| | PROVIDED SHOW 2014. PROVIDE CORRECT COPIES LISTED AS |
| | 2017. FBC 107.2.1 |
| | |
| | 4) YOUR ISOMETRIC PLAN SHOW A NEW 500 GALLON L.P TANK |
| | BUT ON YOUR FLAT DRAWING YOU SHOW A NEW NAT GAS METER |
| | AS BEING THE SOURCE OF GAS PROVIDED. PLEASE CLARIFY |
| | WHICH GAS IS BEING USED. FBC 107.2.1 |
| | |
| | 5) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 6) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| | GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED |
| | PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| | 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED |
| | PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK |
| | SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT |
| | WIND LOAD PER THE FLORIDA BUILDING CODE. |
| | |
| | 7) ) SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW |
| | GRADE. COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 8) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| | THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| | BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC. |
| | 6.6.1.6. |
| | |
| | 9) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| | NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| | MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| | ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. |
| | |
| | 10) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4 |
| | (28) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |