Plan Review Notes
Plan Review Notes For Permit 18011280
Permit Number 18011280
Review Stop G
Sequence Number 1
Notes
Date Text
2018-02-16 07:26:4002/16/2018 GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) GAS REGULATOR MANUAL PROVIDED IS MISSING PAGES 4-10.
 COMPLETE MANUAL IS REQUIRED, 2017 FBC- FUEL GAS 410.1
  
 2) REQUIRED SEDIMENT TRAP FOR THE GENERATOR IS MISSING
 ON YOUR ISOMETRIC PLAM AND I WAS UNABLE TO LOCATE ONE
 BUILT IN THE GENERATOR FROM THE MANUAL SUPPLIED. 2017
 FBC FUEL GAS 408.4
  
 3) YOUR ISOMETRIC DRAWING LIST THE CORRECT 2017 FBC
 FUEL AND GAS CODE BUT THE COPIES OF THE SIZING CHARTS
 PROVIDED SHOW 2014. PROVIDE CORRECT COPIES LISTED AS
 2017. FBC 107.2.1
  
 4) YOUR ISOMETRIC PLAN SHOW A NEW 500 GALLON L.P TANK
 BUT ON YOUR FLAT DRAWING YOU SHOW A NEW NAT GAS METER
 AS BEING THE SOURCE OF GAS PROVIDED. PLEASE CLARIFY
 WHICH GAS IS BEING USED. FBC 107.2.1
  
 5) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 6) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED
 PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK
 SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT
 WIND LOAD PER THE FLORIDA BUILDING CODE.
  
 7) ) SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW
 GRADE. COMPLY WITH NFPA 58 SEC. 6.6.6.1.
  
 8) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
  
 9) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 10) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER