| Plan Review Notes For Permit 18011264 |
| Permit Number |
18011264 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-02-13 16:41:08 | RESIDENTIAL (R3) RE-ROOF, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- TU PUS FLORIDA PRODUCT APPROVAL FL5259-R27 AND FRSA | | | REVISED TABLE 1A SUBMITTED: THE BASIC WIND SPEED FOR | | | THE CITY OF WEST PALM BEACH IS 170MPH NOT 140 MPH. | | | REVISE AS REQUIRED. NEED TO REVISE THE UNDERLAYMENT | | | SYSTEM TO BE INSTALLED TO MEET THE REVISED DESIGN | | | PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|