| Date |
Text |
| 2018-02-05 10:40:43 | DENIED |
| | |
| | 1. TANK-LESS WATER HEATER REQUIRES A SEPARATE PERMIT |
| | FOR GAS. INDICATE ON THE PLAN IF THE TANK-LESS WATER |
| | HEATER IS REPLACING AN EXISTING TANK-LESS WATER HEATER |
| | OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR |
| | IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM? WPB |
| | AMENDMENTS TO THE FBC SEC 105.1 |
| | |
| | 2. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING A PIPING |
| | RISER DIAGRAM AND A DRAWING SHOWING THE LOCATION OF TWH |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. INDICATE ON THE PLAN IF |
| | THE TANK-LESS WATER HEATER IS THE ONLY GAS APPLIANCE IN |
| | THIS SYSTEM? IF NOT, SUBMIT A COMPLETE GAS RISER |
| | SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED |
| | LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE OF GAS AND |
| | THE TOTAL BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS |
| | ALSO APPLY TO A NEW GAS SYSTEM. THE LOCATION OF THE |
| | WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMENDMENTS TO THE FBC SEC 107.2.1. |
| | |
| | 3. CPVC PIPE OUTSIDE IS NOT RECOMMENDED BY MANUFACTURES |
| | SPECIFICATION PLEASE TELL ME HOW YOU ARE GOING TO |
| | PROTECT IT FROM UV EXPOSURE. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC R |
| | SEC G2413.3. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC R SEC G2413.2. |
| | |
| | 6, SUMMIT TANKLESS WATER HEATERS MANUFACTURES |
| | SPECIFICATION AND MUST BE ON SITE FOR INSPECTION |
| | REFERRERS. |
| | |
| | 7. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC 107.2.1. |
| | |
| | 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC R SEC |
| | G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 9. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC FG 410.1. |
| | |
| | 10. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. WPB AMENDMENTS TO THE FBC SEC 109.3 |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW |
| | 561-805-6720 |
| | [email protected] |
| | |
| | |
| | |